Det-Tronics U7698A, B, C, E Unitized Frequency IR Detector/Controller User Manual

Page 4

Advertising
background image

These characteristics are important because fire is a
chemical process, and chemical processes can vary
significantly, depending on the elements and conditions.
A simple fire detector can be designed to detect any
one of these elements, but unless this detector is able to
discriminate, it will be subject to false alar ms.
Discrimination can be achieved by using more than one
element as criteria to detect a fire.

The U7698B detects two elements of fire: IR radiation
and flame flicker. IR radiation is found throughout
nature, but few things emit IR at the flicker frequency of a
fire.

To ensure a high degree of reliability, precision optical fil-
ters limit IR response to a narrow band from 4.2 to 4.7
microns. This bandwidth is significant for two reasons:

1.

Hydrocarbon fires emit intense IR radiation in this
band.

2.

Atmospheric transmission of IR from the sun in the
4.2 to 4.7 micron range is nearly zero. See Figure 1.

Refer to Figure 2 for a block diagram of the U7698B.
Optical filters limit the radiation reaching the sensor to
the range of 4.2 to 4.7 microns. The pyroelectric sensor
converts the infrared energy to an electrical signal.

A flicker filter checks for flame flicker. Any signal that
does not meet the flicker frequency requirements, such
as steady state IR emissions, is rejected. The flicker rate
is set at the factory for levels characteristic of a hydro-
carbon fire (2 to 10 Hz). This flame criteria for the IR
detector results in reliable response to the presence of
fire combined with a high level of immunity from false
alarms.

If the signal meets the requirements for a fire output (IR
radiation of adequate amplitide, with proper wavelength
and flicker frequency, and lasting for approximately 3
seconds), the signal processing circuitry triggers an out-
put circuit, which energizes the alarm relay coil.

OUTPUTS

The U7698B is furnished with two output relays. The
relays have Form C (normally open/normally closed)
contacts and are rated for 2 amperes at 30 vdc. The
normally de-energized fire relay is energized upon
detection of a fire that meets the previously described
flame recognition criteria. It is also field programmable
for either latching or non-latching operation. When
latching operation is selected, the relay is reset by
removing input power for a minimum of 2.0 seconds.
The normally energized fault relay is de-energized upon
loss of input power to the detector or if the sensor mod-
ule is removed.

OPTICAL

FILTERS

IR

SENSOR

FLICKER

FILTER

FIRE

RELAY

NO

COM

NC

A1290

SIGNAL

PROCESSING

CIRCUITRY

POWER

SUPPLY

FAULT

RELAY

INPUT

SUPPLY

VOLTAGE

NO

COM

NC

oi

TEST

oi

Figure 2—U7698B Block Diagram

5.0

4.0

3.0

2.0

1.5

1.0

0.9

0.8

0.7

0.6

0.5

0.4

0.3

0.2

0.1

ATMOSPHERIC

TRANSMISSION

WAVELENGTH (MICRONS)

SOLAR RADIATION REACHING THE EARTH

VISIBLE

INFRARED

ULTRAVIOLET

100

75

50

25

0

A1295

INFRARED SENSOR RESPONSE

Figure 1—Atmospheric Transmission of the Sun's Radiation

2

Advertising