Two LEDs are located inside the detector viewing win-
dow and are illuminated whenever the fire relay is ener-
gized.

oi FEATURE

The U7698B is equipped with the Optical Integrity (

oi)

feature (manually initiated). This patented system
assures proper operation of the detector by checking
the cleanliness of the optical surfaces, sensitivity of the
IR sensor, and proper functioning of the electronic cir-
cuitry. The

oi test is accomplished without the use of an

external IR source. It can be performed at any time by
the operator in the control room by simply pressing a
button. (Fire response equipment must be disabled dur-
ing the

oi test to prevent actuation.) The normally open

switch used to activate the manual

oi test must be con-

nected between the “

oi” terminal and the “–” of the

power supply. The “

oi” terminal must be at less than 0.1

volt to activate the

oi test.

The

oi system generates a low level flickering IR test

beam using two small IR test lamps that are located
inside the detector enclosure. An optical shield prevents
this test beam from reaching the sensor directly.
Instead, the test beam travels through the viewing win-
dow where it strikes a reflective

oi ring and is directed

back through the window and into the sensor. See
Figure 3. The sensor then generates an electrical signal
that is processed by the circuitry in the controller. A suc-
cessful

oi test results in activation of the alarm relay and

illumination of the red LEDs inside the detector viewing
window. If the detector optics are dirty or an IR module
problem has caused a decrease in sensitivity to the
point where approximately 50% of the detection range is
lost, the detector will fail the

oi test. Since the oi test

beam must pass through the same portion of the viewing
window as IR radiation generated by a fire, the

oi sys-

tem provides a reliable test of the ability of the detector
to “see” a fire. The fault relay is unaffected by the

oi

test.

DETECTOR ENCLOSURE

The U7698B features an explosion-proof housing that is
designed for installation in hazardous locations in both
indoor and outdoor environments. The detector is not
affected by adverse weather conditions such as wind,
rain, snow, high humidity, or extremes of temperature or
pressure.

SPECIFICATIONS

OPERATING VOLTAGE—
24 vdc nominal, 18 to 32 vdc maximum.

POWER CONSUMPTION—
1.0 watt nominal, 3.5 watts maximum during

oi test.

POWER ON DELAY—
8 seconds. The fault relay will energize in less than 1
second.

OUTPUT RELAYS—
The U7698B has two Form C (N.O. and N.C.) relays.
The normally de-energized alarm relay is programmable
for either latching or non-latching operation. The nor-
mally energized fault relay is de-energized in the event
of a power failure or removal of the IR module.

RESET TIME—
Reset requires 0 volts at the detector for 2.0 seconds
(when latching operation is selected).

RELAY CONTACT RATING—
Form C, rated 2 amperes at 30 vdc.

SPECTRAL SENSITIVITY RANGE—
4.2 to 4.7 microns.

CONE OF VISION—
80 degree cone of vision. See Figure 4 .

IR DETECTOR

IR TEST LAMP (2)

IR SENSING ELEMENT

SNAP-IN

oi

RING

OPTICAL FILTER

VIEWING WINDOW

A1291

Figure 3—Optical Integrity Feature

3

95-8353

0

°

15

°

30

°

45

°

15

°

30

°

45

°

A1461

100

90

80

70

60

50

40

30

20

10

DETECTION

DISTANCE

(PERCENT)

100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A

GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF

INCIDENCE DECREASES.

Figure 4—Cone of Vision