Elkhart Brass Scorpion RF 8394-07 User Manual

Page 16

Advertising
background image

16

VERTICAL TRAVEL STOP IS FACTORY
SET AT 90 ABOVE TO 45 BELOW
HORIZONTAL

STOP SCREWS ARE FACTORY
INSTALLED AT THESE LOCATIONS.
(180 HORIZONTAL TRAVEL.)

Rotational Limit Settings
8294-06

The rotational stop screws (see Figure 4) set the monitor rotational limits (left-right and up-down)

to satisfy the application requirements, as well as NFPA* requirements. The monitor is shipped

from the factory with the horizontal travel limits set at 90 degrees left and 90 degrees right of

the zero (straight ahead) position. The vertical travel limits are factory set at 90 degrees above,

and 45 degrees below horizontal. If the application requires the rotation limits to be changed,

relocate threaded stop screws to required positions per chart below. Apply Loctite 242 or

equivalent to stop screws and hex head plugs prior to reinstalling (stop screw holes are identified

on the monitor by a stamped letter adjacent to each hole). All empty stop screw holes should be

filled with a hex head plug.

8394-07

The rotational stop screws (see Figure 4) set the monitor rotational limits (left-right and up-down)

to satisfy the application requirements, as well as NFPA* requirements. The monitor is shipped

from the factory with the horizontal travel limits set at 90 degrees left and 90 degrees right of

the zero (straight ahead) position. The vertical travel limits are factory set at 90 degrees above,

and 45 degrees below horizontal. If the application requires the rotation limits to be changed,

relocate threaded stop screws to required positions per chart below. Apply Loctite 242 or

equivalent to stop screws and hex head plugs prior to reinstalling (stop screw holes are identified

on drawing 98031050). All empty stop screw holes should be filled with a hex head plug

8294-06 EXT

Monitor can be rotated 90° left or 90° right of the zero (straight ahead) position. The vertical

travel is either Master Stream (+30 to -135°) or Egress (+0° to -135°). Horizontal travel limits

can NOT be changed.

Monitor can be rotated 90° left or 90° right of straight ahead. Stops are mechanically fixed by a

stop screw and milled slot in base. Stop screw must remain in place in monitor base.

Figure 4: Scorpion RF Rotational Stops

VERTICAL TRAVEL STOP IS FACTORY
SET AT 90 ABOVE TO 45 BELOW
HORIZONTAL

STOP SCREWS ARE FACTORY
INSTALLED AT THESE LOCATIONS.
(180 HORIZONTAL TRAVEL.)

Advertising
This manual is related to the following products: