Caution – Elkhart Brass Scorpion RF 8394-07 User Manual

Page 17

Advertising
background image

17

Caution:

At least one stop screw is required to prevent damage to the monitor. If the

monitor is set with the horizontal setting at 174 degrees left or right of the zero (straight
ahead) position, the vertical setting will need to be set to 30 degrees below horizontal as
the maximum lowest position.



Table 3: Horizontal Settings (8294-06 only)

Application

Rotation Limits

Stop Screw

Locations

Aerial Ladder,

Elevating Platform,

Water Tower

45° Left or Right of Straight Ahead

D & H

67½° Left or Right of Straight Ahead

E & G

90° Left or Right of Straight Ahead

F

Deck Gun

174° Left or Right of Straight Ahead

A

Table 4: Vertical Settings (8294-06 only)

Application

Rotation Limits

Stop Screw

Locations

Aerial Ladder,

Deck Gun

90° above horizontal to 45° below horizontal

T

Elevating Platform 45° above horizontal to 45° below horizontal

T & U

To view a complete list of stops, please download the Scorpion Monitor Position Chart (98031010 for

8294-06, and 98031050 for 8394-07) from

www.elkhartbrass.com

.

Table 5: NFPA 1901, 2003 Ed. minimum rotation angles for aerial device monitors.

20.6

Aerial Ladder Water Delivery System

20.6.1.3.1

The monitor shall be capable of swiveling at least 135° from a line parallel to the

ladder and down.

20.6.1.3.2

The monitor shall be capable of horizontal traverse at least 45° from each side of

center.

20.12

Elevating Platform Water Delivery System

20.12.3.2

The monitor(s) shall allow the operator to control the aimed direction of the nozzle

through a rotation of at least 45° on either side of center and at least 45° above and

below horizontal.

20.12.3.3

The horizontal and vertical traverse of the monitors shall not exceed the elevating

platform manufacturer’s recommendation.