Figure 2: MMCP Fuse and Jumper Diagram

Figure 3: MMCP - OCP Wiring Chart

Figure 1: MMCP Fuse and Jumper Diagram

Figure 4: MMCP – Monitor Junction Box

Wiring Chart

MMCP Fuse and Wiring































WIRE SIZE FOR CONDUCTORS BETWEEN

MONITOR MOTOR CONTROL PANEL AND

OPERATOR CONTROL PANEL OR VALVES

CONDUCTOR LENGTH

WIRE SIZE

UP TO 750 FEET (228.6 m)

18-AWG

750 TO 1500 FEET (457.2 m)

16-AWG

1500 TO 2500 FEET (762 m)

14-AWG

2500 TO 3500 FEET (1066.8 m)

12-AWG

WIRE SIZE FOR CONDUCTORS BETWEEN

MONITOR MOTOR CONTROL PANEL AND

MONITOR JUNCTION BOX

CONDUCTOR LENGTH

WIRE SIZE

UP TO 75 FEET (22.86 m)

18-AWG

75 TO 100 FEET (30.48 m)

16-AWG

100 TO 200 FEET (60.96 m)

14-AWG

200 TO 400 FEET (121.92 m)

12-AWG