Elkhart Brass SPIT-FIRE 8394059 Monitor User Manual

Page 7

Advertising
background image

7

Power converts to 24
VDC in control panel

III SPECIFICATIONS

General Specs

 Input Power

120/240 VAC (50/60Hz.) 1 Phase
480 VAC (50/60 Hz.) 3 Phase
500 VA max. Power

 Electrical Load

4 AMPS MAX

 Panel Dimensions

24” X 36” (609.60mm X 914.40mm)

 Panel Weight

Approx. 100 lbs

 Operating Temperature Range -10

o

C to +70

o

C

ATEX Product Marking

II 3 G c

Ex nA nC II T3



IV OPERATING INSTRUCTIONS

This control panel has one ON/OFF 2-position selector switch. Move it to the ON position so the pilot light
illuminates, showing the panel is now powered up, and ready for associated monitor operation.



V MAINTENANCE

Monthly Inspection and Maintenance

1. Check the indicator light and replace bulb if it’s not operable.
2. Confirm that all terminal blocks and connections are properly taut to 4.5 – 7.1 in-lbs. (0.508 – 0.802

Nm).

3. Check for proper operation of the system overall, if there are problems with the system please refer to

the Troubleshooting section for help.