VI TROUBLESHOOTING

A. If Panel will not power up:

1. Check the incoming supply power, and if it’s the proper power requirement for the system.
2. Check to make sure the transformer is wired correctly.
3. Check fuses in panel to confirm they are good. If fuses are blown, replace them with same or

equivalent fuse.

a. Check for causes in the interconnect wiring and connections.
b. Verify that the OCP/NCP is not trying to activate the monitor motor functions
c. If nothing is found consult with your Elkhart Brass representative.

4. Check panel power switch to make sure it is in the “Power On” position.
5. Check power supply to confirm there is 120 VAC running to it.

B. If Pilot Light is not on when panel has power:

1. Check the light bulb, and replace if it is burnt out.

C. Function not working correctly:

1. Check to see if there is a loose connection at the terminal blocks or contact blocks. Make sure all

screw terminations are properly tightened to 4.5 – 7.1 in-lbs (0.508 – 0.802 Nm)

2. Check relay for actuation. If bad, replace relay with new working relay.

D. Water or Foam valve will open but will not close when operated.

1. Verify that jumpers between terminals (10 and 14) or (15 and 19) are removed.


Please refer to our website at

www.elkhartbrass.com

for any further information. Any problems that

cannot be fixed/solved should be taken to your Elkhart Brass Representative.

WARNING:

Do not attempt to disconnect or work on any electrical equipment in this

system unless power is removed or the area is known to be non-hazardous.