Installation Environment Requirements

For your own safety, install a main circuit breaker cabinet or other readily accessible
power disconnect in the same area as the DRd enclosure. For cross-bussed
installations, this device may be the auxiliary enclosure. Main breakers not in the same
room must have a physical means to be locked off. ETC recommends adopting lockout
/ tagout procedures for your facility and following appropriate Lockout/Tagout
procedures as described in NFPA Standard 70E.

A clean (not dusty) temperature-controlled environment with an ambient temperature
of 32-104°F / 0-40°C and ambient humidity of 10-90%, non-condensing.

Restricted public access to prevent tampering.

Soundproofing or performance area separation to muffle ventilation fan noise is
recommended.

All CE equipment is tested to EMC category B environment.

Wire Routing and Specification

When planning wire entry into the enclosure, notice that conduit knockouts are provided

only on the sides of the unit. These knockouts are primarily used for bussing to an auxiliary

enclosure but may also be used for load or control wiring. Signal and power wiring must be

run in separate conduit per local code.

Due to the bend radii of certain size line feed wires and the location of terminations, special

attention is required for line feed wire entry. Reference the wiring guidelines below for

recommendations.

C A U T I O N :

HVAC systems must at all times maintain the specified ambient temperature at the

enclosure. Dimming systems operating within 10°F (5°C) of the upper or lower

temperature limits must strictly follow installation and operation guidelines to

operate reliably.

C A U T I O N :

Do not route line (input feed) wires through the back panel. Doing so requires bend

radii that violate NEC code, UL standards and because of undue stress at the wire

joint is likely to create a poor connection.
Line and load wire used with Unison DRd enclosures must be copper. Load wires

may either be stranded (preferred) or solid core. The use of aluminum wire is not

allowed in DRd enclosures.
Aluminum feed wires are supported only in the auxiliary (AX Series) enclosures.

Wire Access

Location

Wire Size

DRd12 Feed

(max)

350 Kcmil

185mm

2

DRd6 Feed

(max)

2/0-3

70mm

2

Load Wires

12 - 6AWG

2.5 - 16mm

2

Control

Wires

Top

acceptable

acceptable

acceptable

acceptable

Bottom

acceptable

acceptable

acceptable

preferred

Left side

Do Not Use

Do Not Use

acceptable

acceptable

Right side

Do Not Use

Do Not Use

acceptable

acceptable