Terminate Wiring

33

Connect Control Wiring

Overview

All low voltage data and option wiring connects to pluggable connectors on the left and right

I/O boards near the bottom of the DRd enclosure.

The DRd ships with a right side I/O board for low voltage control connections. Left side I/O

board is available in the optional Paradigm and Echo Termination Kits.

The Paradigm Left I/O Kit supports contact inputs and outputs, serial RS232 and
Ethernet control. This Left I/O board is not compatible with the SmartLink or Echo
Architectural Control Processors.

The Echo Network Kit supports an Ethernet connection for the Echo ACP. The Echo
Network Kit is not compatible with the SmartLink or Paradigm ACPs.

The right side I/O board is shipped installed with each DRd and provides termination
for SmartLink / LinkConnect / EchoConnect, auxiliary power, DMX, and a UL 924
emergency contact input. The DRd enclosure supports option kits which install in the
bottom of the DRd for extended control and operation and terminate to the right I/O
board. Option modules include:

0-10V Control Option (DRd-FLO) which provides 24 outputs for control of 0-10V
(4-wire) control for LED drivers and fluorescent ballasts. Each channel output is
linked one-to-one with a circuit for power control.

Digital Addressable Lighting Interface (DRd-DALI) which provides 24 outputs for
control of DALI-compatible fluorescent ballasts. Each channel output of DALI
control is linked one-to-one with a circuit for power control (DALI Broadcast Mode).

Unison RideThru kit provides power to the ACP during brief power outages or drop
outs. The URTO sustains power to the ACP for at least 12 seconds.

Unison BatteryPack kit sustains power to the ACP for up to 90 minutes during
power outages.

N o t e :

All low voltage control cables must run in separate conduit from power wires.

N o t e :

A DRd enclosure supports the use of either a DALI option board (DRd-DALI) or

the FLO option board (DRd-FLO), but not both.

1
2

3
4

5
6

7
8

9

10

11
12

13
14

15
16

17
18

19
20

21
22

23
24

3

Right I/O board -

ships standard with

each DRd enclosure.

Left I/O board is

available as part of the

Paradigm Termination

Kit which ships with

the Paradigm ACP.

An optional Left I/O kit

is available for use

with Echo ACP when

DRd is being used in a

networked system.

The enclosure door has

been removed from these

graphics for clarity of the

procedure.