Typical operating distance, Only in combination with ces-a-bba actuator) – EUCHNER CES-AR-C01-CH-SA (Multicode) User Manual

Page 26

Advertising
background image

Operating Instructions Safety Switch CES-AR-C01-CH-SA

26

Switching distances
Operating distance for center offset m = 0

(only in combination with CES-A-BBA actuator)

Parameter

Value

Unit

min.

typ.

max.

Switch-on distance

-

18

-

mm

Assured switch-on distance s

ao

1)

15

-

-

Switching hysteresis

1)

1

3

-

Assured switch-off distance s

ar

-

-

45

1) The values apply for surface installation of the actuator.

Typical operating distance

(only in combination with CES-A-BBA actuator)

Figure 7: Typical operating distance

X

25

15

20

10

5

20

25

30

5

10

15

-30

30

-30

25

20

15

10

5

Y

Z

For a side approach direction for the actuator and safety switch, a minimum distance of s = 4 mm

must be maintained so that the operating distance of the side lobes is not entered.