Easco boiler, Series boiler – Beckett BRYAN STEAM CF2500A User Manual

Page 18

Advertising
background image

Easco Boiler

SM5

Series Boiler

Boiler

Burner

Chassis

Spec.

Air Tube

Combination

High

Fire
Rate

Nozzle

Head

Setting

Blue -

Low Fire

Air or

Shutter

Red -

High Fire

Air or

Band

Low Fire

Pump

Press.

High Fire

Pump

Press.

Pressure

Firing
Flange

Insertion

20

CF800

BCF403

CF100KH

5.80

4.50x45P

3

10

3

150

N/A

51628

5.00"

25

CF1000

BCF101

CF102KD

7.30

4.00x45P

4

20

N/A

300

N/A

51629

5.00"

30

CF1400

BCF205

CF102KE

8.70

5.00x45P

7

20

40

150

300

51629

5.00"

35

CF1400

BCF205

CF102KE

10.20

5.50x45P

9

30

70

150

300

51629

5.00"

40

CF2300A

BCF304

CF102KG

11.70

7.00x45P

0

16

30

150

275

51630

5.00"

50

CF2300A

BCF304

CF102KG

14.60

8.50x45P

3

20

40

150

275

51630

5.00"

60

CF2300A

BCF304

CF102KG

17.50

10.00x45P

6

20

70

150

300

51630

5.00"

60S

CF2300A

BCF304

CF102KG

17.50

10.00x45P

6

20

70

150

300

51630

5.00"

70

CF2500

BCF1801

CF102KP

20.40

6.00x45P (2)

8

40

90

275

275

51630

5.00"

80

CF3500

BCF1301

CF80KM

23.30

6.50x45P (2)

7

30

80

300

300

51630

5.00"

90

CF3500

BCF1301

CF114KR

26.20

7.50x45P (2) 7-1/2

40

90

300

300

51631

5.00"

100

CF3500

BCF1301

CF114KR

29.20

8.50x45P (2)

8

50

100

280

280

51631

5.00"

Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.

Flange requires an additional adapter plate.

Page 17

Advertising