Smith Cast Iron Boilers

18

Series Boiler

Boiler

Burner

Chassis

Spec.

Air Tube

Combination

High

Fire
Rate

Nozzle

Head

Setting

Blue -

Low Fire

Air or

Shutter

Red -

High Fire

Air or

Band

Low Fire

Pump

Press.

High Fire

Pump

Press.

Pressure

Firing
Flange

Insertion

18-4

CF500

BCF809

CF60KK

2.55

2.25x60PLP 1-1/2

4

0

N/A

140

51628

3.875"

18-5

CF500

BCF809

CF60KK

3.25

2.75x60PLP

3

5

0

N/A

140

51628

3.875"

18-6

CF500

BCF809

CF60KK

4.00

3.50x60PLP

5

10

4

N/A

140

51628

3.875"

18-7

CF500

BCF809

CF60KK

4.70

4.00x60PLP

6

10

10

N/A

140

51628

3.875"

18-7

CF800

BCF403

CF60KJ

4.70

4.00x60PLP

1

7

0

N/A

140

51628

3.875"

18-8

CF800

BCF403

CF60KJ

5.40

4.50x60PLP

2

10

0

N/A

140

51628

3.875"

18-9

CF800

BCF403

CF60KJ

6.10

5.00x60PLP

4

10

3

N/A

140

51628

3.875"

18-10

CF800

BCF403

CF60KJ

6.90

6.00x60PLP

5

10

8

N/A

140

51628

3.875"

18-10

CF1400

BCF205

CF66KD

6.90

4.00x45PLP

3

25

60

125

300

51629

3.875"

18-11

CF1000

BCF101

CF66KE

7.60

4.50x45PLP

4

20

N/A

N/A

300

51629

3.875"

18-11

CF1400

BCF205

CF66KD

7.60

4.50x45PLP

4

30

60

125

300

51629

3.875"

18-12

CF1000

BCF101

CF66KE

8.30

5.00x45PLP 4-1/2

21

N/A

N/A

300

51629

3.875"

18-12

CF1400

BCF205

CF66KD

8.30

5.00x45PLP

5

25

70

125

300

51629

3.875"

Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.