Burnham corporation, Series boiler – Beckett BRYAN STEAM CF2500A User Manual

Page 9

Advertising
background image

Burnham Corporation

V11

Series Boiler

Boiler

Burner

Chassis

Spec.

Air Tube

Combination

High

Fire
Rate

Nozzle

Head

Setting

Blue -

Low Fire

Air or

Shutter

Red -

High Fire

Air or

Band

Low Fire

Pump

Press.

High Fire

Pump

Press.

Pressure

Firing
Flange

Insertion

V1104

CF1400

BCF205

CF66KD

5.80

3.50x45P

0

25

50

150

300

51629

4.12"

V1105

CF1400

BCF205

CF66KE

7.40

4.50x45P

0

30

50

150

300

51629

4.12"

V1106

CF1400

BCF205

CF66KE

9.20

5.50x45P

2

30

60

150

300

51629

4.12"

V1107

CF2300A

BCF304

CF66KG

11.00

6.50x45P

2

30

60

150

300

51630

4.00"

V1108

CF2300A

BCF304

CF66KG

13.00

7.50x45P

4

35

60

150

300

51630

4.12"

V1109

CF2300A

BCF304

CF66KG

14.80

8.50x45P

4

35

75

150

300

51630

4.12"

V1110

CF2300A

BCF304

CF66KS

16.60

9.50x45P

4

30

55

150

300

51630

4.12"

V1111

CF2300A

BCF304

CF66KS

18.40

10.50x45P

6

40

60

150

300

51630

4.12"

V1112

CF2500A

BCF1801

CF66KP

20.00

5.50x45P (2)

4

20

45

300

300

51630

4.12"

V1113

CF2500A

BCF1801

CF66KP

21.50

6.00x45P (2)

5

22

55

300

300

51630

4.12"

V1114

CF3500

BCF1301

CF80KM

23.50

6.50x45P (2)

2

25

80

300

300

51630

4.12"

V1115

CF3500A

BCF1301

CF80KM

25.50

7.00x45P (2)

3

30

90

300

300

51630

4.12"

V1116

CF3500A

BCF1301

CF114KR

27.00

7.50x45P (2)

6

32

85

300

300

51631

5.50"

Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.