HYDAC HDA 5500-3-2-DC-000 User Manual

Page 10

Advertising
background image

HDA 5500 User Manual

- 10 -

Menu point

Setting

Setting range

Default setting

Decimal place sensor 1 (dEc.1)

No. of decimal place(s) of the display of measured value of
sensor 1

0..0.000

0.0

Lower display range sensor 1 (LOr.1)

Lower limit of the display range of sensor 1

-999..9899

0

Upper display range sensor 1 (Hir.1)

Upper limit of the display range of sensor 1

-899..9999

100.0

Background lighting for the unit label for sensor 1 (uni.1)

Lighting behind unit label is switched on when

value of sensor 1 is displayed.

Lighting behind unit label is switched off when

value of sensor 1 is displayed.

on
oFF

on

Decimal place Pt 100 sensor (dEc.2)

No. of decimal place(s) of the display of measured value of
Pt 100 sensor

0..0.000

0.0

Lower display range Pt 100 sensor (LOr.2)

Lower limit of the display range of Pt 100 sensor

-999..9899

0

Upper display range Pt 100 sensor (Hir.2)

Upper limit of the display range of Pt 100 sensor

-899..9999

100.0

Background lighting for the unit label for Pt 100 sensor
(uni.2)

Lighting behind unit label is switched on when

value of Pt 100 sensor is displayed.

Lighting behind unit label is switched off when

value of Pt 100 sensor is displayed.

on
oFF

on

Calibration of the sensor zero point (CALi.)

The actual measurement is saved as the new zero

point. This is possible in the range +/- 2.5 % of the
display range.

is displayed if a calibration has been

carried out in the permitted range.

is displayed if a calibration has not

been possible.

The function is useful for example, if the output signal always
has an offset which should be displayed as the zero point.

Actual measured value is not to be saved.

YES
no

no