MOUNTING THE CONTROL

STEP 1

Two mounting positions are available on the

back of the control (Fig. 1). Select which of the two positions

(2 knockouts) is best for the location of the control. Remove

the knockout.

STEP 2

Place control on the well. While holding box

against well nut, tighten well clamp screw. (Fig. 2)

BACK OF HYDROSTAT BOX

FIG. 1

FIG. 3

FIG. 2

NOTE: In the case of space restrictions, the HydroStat con-

trol may be mounted in a horizontal orientation without any

loss of function. Hydrolevel recommends vertical mounting,

when possible, for proper orientation of LED display.

STEP 3

Insert sensor ALL THE WAY into well through

the knockout (A or B) you have chosen. (Fig. 3)

IMPORTANT

Make sure that the immersion well or Electro-Well™ is installed on the boiler manufacturerʼs

designated temperature limit control tapping. Note: If installing an Electro-Well, pipe sealing compound should be

used. Teflon tape is not recommended.

REMOTE MOUNTING

The following kits are available separately for mounting

the HydroStat control box in a remote location. Each kit

includes mounting hardware and a remote sensor.

Part No.

Description

48-101

Wall/Jacket Mounting Kit with 2' sensor cord

48-102

Wall/Jacket Mounting Kit with 4' sensor cord

48-103

Wall/Jacket Mounting Kit with 10' sensor cord

48-104

Wall/Jacket Mounting Kit with 20' sensor cord

48-121

Pipe Mounting Kit with 4' sensor cord