Warm start, Cold start, 4setting the control – Hydrolevel 3100 User Manual

Page 4: Operation

Advertising
background image

4

SETTING THE CONTROL

To set COLD START operation

Operates on call for heat only.

Low Temperature Limit

Make sure Low Temperature Limit is turned fully counter-

clockwise (OFF position).

Low Temperature Differential

No change is required.

High Temperature Limit

(factory setting = 190°F)

Adjust setting until desired temperature is displayed.

High Temperature Differential

(factory setting = 10°F)

Using a small screwdriver, adjust setting until desired differ-

ential is displayed.

To set WARM START operation

Maintains temperature for domestic hot water.

Low Temperature Limit

Adjust setting until desired temperature is displayed.

Low Temperature Differential

Using a small screwdriver, adjust setting until desired differ-

ential is displayed.

High Temperature Limit

(factory setting = 190°F)

Adjust setting until desired temperature is displayed.

High Temperature Differential

(factory setting = 10°F)

Using a small screwdriver, adjust setting until desired differ-

ential is displayed.

WARM START

(maintains temperature for domestic hot water)

Low Limit Switch = ON

COLD START

Low Limit Switch = OFF

Example

High Limit = 180°

Differential = 10°

On a call for heat, the burner will
shut off at 180° and restart at
170° (180°-10°). The circulator
will run as long as there is a call
for heat.

High Temperature Limit

(Adjustable 100° to 220°F)
De-energizes burner at HIGH
LIMIT setting

High Temperature Limit

(Adjustable 100° to 220°F)
De-energizes burner at HIGH
LIMIT setting

High Temperature
Differential

(Adjustable 10° to 30°F)
Re-energizes burner when
temperature falls to the HIGH
LIMIT DIFFERENTIAL set point

High Temperature
Differential

(Adjustable 10° to 30°F)
Re-energizes burner when
temperature falls to the HIGH
LIMIT DIFFERENTIAL set point

Low Temperature Limit

(Adjustable 110° to 200°F)
De-energizes burner at LOW
LIMIT setting

Low Temperature
Differential

(Adjustable 10° to 30°F)
Re-energizes burner when
temperature falls to the LOW
LIMIT DIFFERENTIAL set point

Example

High Limit = 180°

Differential = 10°

On a call for heat, the burner will
shut off at 180° and restart at
170° (180°-10°). The circulator
will run as long as there is a call
for heat.

Example

Low Limit = 150°

Differential = 10°

When there is no call for heat,
the burner fires at

140°

(150°-10°) to maintain boiler
temperature. Burner shuts off
at 150°.

NOTE: To prioritize domestic hot
water the HydroStat control will
not allow the circulator to
operate at any time the
temperature is below the low
limit setting.

OPERATION

Dynamic

Display

Water Temperature

and Real Time

Verification of

Setting Adjustments.

All Settings are

Displayed Every

Time Control is

Powered Up

Low Temperature

Limit Setting

(OFF or 110°-200°F)

Factory OFF

Low Temperature

Differential Setting

(10°-30°F)

Factory 10°F

High Temperature

Limit Setting

(100°-220°F)

Factory 190°F

Diagnostic LEDs

High Temperature

Differential Setting

(10°-30°F)

Factory 10°F

NOTE: Be careful not to select overlapping temperature settings.

For example: If the HIGH TEMPERATURE LIMIT is set at

190°F with a HIGH TEMPERATURE DIFFERENTIAL set at 20°F,

then the LOW TEMPERATURE LIMIT needs to be set at 170°F

(190°F - 20°F = 170°F) or below.
IMPORTANT: To prevent flue gas condensation and reduce fatigue

caused by thermal cycling on conventional (non-condensing) boilers,

both HIGH and LOW LIMIT set points should be 150°F or above

(Limit Setting - Differential Setting ≥ 150°F). Boiler manufacturerʼs

temperature requirements supercede these recommendations.