SPECIFICATIONS

HYDROSTAT MODEL 3100

DIMENSIONS

LOW WATER CUT-OFF TEST PROCEDURE

ELECTRO-WELLS

LIMITED MANUFACTURERʼS WARRANTY

We warrant products manufactured by Hydrolevel Company to be free from defects in

material and workmanship for a period of two years from the date of manufacture or

one year from the date of installation, whichever occurs first. In the event of any claim

under this warranty or otherwise with respect to our products which is made within

such period, we will, at our option, repair or replace such products or refund the pur-

chase price paid to us by you for such products. In no event shall Hydrolevel Company

be liable for any other loss or damage, whether direct, indirect, incidental or conse-

quential. This warranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other

warranty or guarantee, express or implied, including, without limitation, any warranty

of MERCHANTABILITY or fitness for a particular purpose. This warranty may not be

assigned or transferred and any unauthorized transfer or assignment thereof shall be

void and of no force or effect.

Input voltage

120 VAC, 60 HZ

Burner contacts

30 VA@24 VAC

Circulator contacts

5.8 FLA, 34.8 LRA@120 VAC

Operating range – low limit

Off or 110°F - 200°F

Operating range – high limit

100°F - 220°F

Operating range – differential 10°F - 30°F

HydroStatʼs low water cut-off function is active when the control is installed on a Hydrolevel Electro-Well. To test the low water

cut-off function:

Turn OFF power to the control.

Set the thermostat to call for heat.

Gently slide the sensor out of the well

to simulate a low water condition.

Turn ON power to the control. The red LOW WATER light should come on and the burner

should not fire.

Turn OFF power again and reinstall the sensor in the well.

Turn ON power to the control. The green LWCO

ACTIVE light should illuminate and the burner should fire.

NOTE: Do not remove the sensor from the well while the control is powered.

MAINTENANCE

Remove the Electro-Well from the heating system every five years and clean any scale or sediment deposits from all parts that

are exposed to the boiler water. After cleaning, reinstall the well using pipe sealing compound. Teflon tape is not recommended.