background image

Single Zone Gas Monitor

6

P/N: 3015-4256 Rev 13

Category

General Single Zone Specifications

Coverage

Single zone

Detector Type

Infrared, Non-Dispersive

Warm-up Time

15 minutes

Front Panel

3 Indicator lights:

• Green Monitor is powered on. LED glows during normal operation; flashes

when unit is in warm-up mode

• Red

Alarm. LED flashes when any point has exceeded the alarm setting.

• Yellow Fault. LED flashes when there is a system fault

Size (HxWxD)

7.5" x 13.5" x 3.625" (190.5 mm x 343 mm x 92 mm)

Weight

5.5 lbs (2.5 kg)

Temperature Drift

Less than 1 ppm per °C between purge cycles

Sampling Mode

Automatic (continuous)

Re-Zero

Automatic (approximately every 5 minutes)

System Noise

Less than 50 dB(A) @ 10 feet (3m)

Monitoring Distance

500 ft. (152 m) maximum

Conditioned Signal

4-20 mA DC non-isolated output (ppm)

Alarms

Four SPDT alarm contacts are provided rated 2A at 250 VAC (inductive), 5 A at
250 VAC (resistive)
Three assigned to PPM level alarms, one assigned to system faults

Power Safety Mode

Fully automatic system reset. All programmed parameters retained.

Operating Temp

32 to 122 °F (0 to 50 °C)

Ambient Humidity

5% to 90% RH (non-condensing)

AC Power

100 to 240 VAC, 50/60 Hz,

15 Watts

Certification

UL 61010-1, CAN/CSA 22.2 No. 61010-1 and CE Mark

Warranty

2 years from date of shipment

Altitude Limit

6,562 ft (2,000 m) maximum

Sensor Life

7-10 years