Appendix b. agency approvals, Eclaration, Onformity – Bacharach 3015-4286 User Manual

Page 38

Advertising
background image

Single Zone Gas Monitor

34

P/N: 3015-4256 Rev 13

APPENDIX B. AGENCY APPROVALS

D

ECLARATION

OF

C

ONFORMITY


The manufacturer of the

products covered by this

declaration:

Bacharach, Inc.
621 Hunt Valley Circle
New Kensington, PA 15068

Year conformity is declared: 2010 (EN 14624), 2008 (all others)
Product(s):

Refrigerant Monitors

Model(s):

HGM-SZ and HGM-MZ (Single and Multi Zone Refrigerant Monitors) (EN 14624 only)
HGM-SZ, AGM-SZ, CO2-SZ, HGM-MZ, AGM-MZ, CO2-MZ and MZ-RD.

The undersigned hereby declares that the above referenced products are in conformity with the provisions of the following

standard(s) and is in accordance with the following directive(s).

Standard(s):

EN 14624

Performance of mobile leak detectors and of room controllers of halogenated refrigerants

EN 61326-1:2006 Electrical equipment for measurement, control, and laboratory use—EMC requirements: Part 1 General Requirements
EN 61010-1:2001 Safety requirement for control, measurement, and laboratory equipment

Directive(s):

2004/108/EC

EMC Directive

2006/95/EC

Low Voltage Directive

Signature:

Name:

Doug Keeports

Title:

VP of Product Development

Date:

06 December 2010

The technical documentation file required by this directive is maintained at the corporate headquarters of Bacharach, Inc.

European Standard EN14624: 2005 testing with R-134a (Halogen Gas Monitor Only).

Min. Sensitivity Threshold

1 ppm

Max. Sensitivity Threshold (within 1 ppm ± 10% reading accuracy range)

1,000 ppm

Max. Sensitivity Threshold within Instrument Reading Range

10,000 ppm

Zeroing Time from 1,000 ppm*

<12 seconds

Zeroing Time from 10,000 ppm*

<25 seconds

Reaction Time for detection of minimum threshold*

≤12 seconds

Min. Sensitivity threshold once max. threshold has been measured

1 ppm

Repeatability at 500 ppm

± 1% of reading

* Based on a minimum tubing length of one foot

Advertising