Specifications – Bacharach 3015-4286 User Manual

Page 9

Advertising
background image

Single Zone Gas Monitor

P/N: 3015-4256 Rev 13

5

1.7. Specifications

Category

HGM-SZ Specifications

Product Type

Single-zone infrared monitoring system for low level continuous monitoring of CFC, HCFC
and HFC refrigerant gasses used in most commercial refrigeration systems. System design
supports compliance to the refrigerant monitoring requirements of ANSI/BSR ASHRAE 15-
2007 and ASHRAE Safety Code 34-2007.

Gas Library:

CFC

HFP, R-11, R-113, R-114, R-12, R-502

HFC

R-125, R-134a, R-236FA, R-245Fa, R-404a (HP62), R-407a, R-407c (AC9000), R-410a
(AZ20), R-422a, R-422d, R-427a, R-507 (AZ50), R-508b (SUVA95)

HCFC

R-123, R-124, R-21, R-22, R-227, R-23, R-401a (MP39), R-402a (HP80), R-402b (HP81),
R-408a, R-409a, R-500, R-503

HALON

H1211, H1301, H2402

Other

FA188, FC72, HFO1234YF, N1230, R-420a, R-424a, R-426a, R-427a, R-438a

Sensitivity

All gasses 1 ppm

Measuring
Range

All gasses 0 to 10,000 ppm

Accuracy

±1 ppm ±10% of reading from 0-1000 ppm

(R11, R22, R113: ±10 ppm ±15% of reading 0-1000 ppm)

Response Time

105 seconds maximum (dependent on sample line length)

Category

AGM-SZ Specifications

Product Type

Single zone infrared monitoring system for low level continuous monitoring of ammonia
refrigerant gas used in most commercial refrigeration systems.

Gas Library

Ammonia / NH

3

/ R-717

Sensitivity

20 PPM (minimum detection limit)

Measuring Range

25-10,000 PPM

Accuracy

±10 ppm ±10% of reading from 25 to 1,000 ppm

Response Time

180 seconds maximum (dependent on sample line length)