31. BACKUP

Backup parameters and save them in the EEPROM memory module.

All of the configuration setting parameters can be saved in the EEPROM memory

module for backup. The backup parameters can then be restored if they have been

inadvertently changed or corrupted. Once backup is complete the EEPROM memory

module may be removed for safe storage. All DPC-12 and DPC-24 control modules

are shipped with the factory default settings saved in the EEPROM memory module.

Press EXECUTE to enter the menu.

DISABLED

This menu is disabled for inadvertent use. Proceed to enable.

ENABLED

Press and hold MENU ( ) and MENU ( ) at the same time for 4-5 seconds.

MEMCHECK

Automatically checks the EEPROM memory module for parameter type.

SURE ???

Press EXECUTE to proceed.

WAIT

Automatically begins parameter backup and generates CRC value.

VERIFY

Automatically verifies parameter backup data and CRC value.

DONE!!

Parameter backup is done and saved in the EEPROM memory module.

NO MEM!

Displayed if an EEPROM memory module is not detected.

WRONG

Displayed if the wrong type (parameter) of EEPROM memory module detected.

MEM TYPE

Displayed if the wrong type (parameter) of EEPROM memory module detected.

WRONG

Displayed if the wrong product type of EEPROM memory module detected.

PRODUCT

Displayed if the wrong product type of EEPROM memory module detected.

DATA ERR

Displayed when a data error occurs. Waits for key press to restart BACKUP.

NOTE: Be sure to BACKUP the DPC-12 or DPC-24 when installation configuration is

complete.

32. PRINTOUT

Print various system configuration settings using a hand held infrared printer.

All DPC-12 and DPC-24 control modules come equipped with an infrared (I/R) LED

that provides the ability to printout all the system configuration settings, when used

in conjunction with a hand held infrared printer (Johnson System Inc., Part Number:

JS-IP). Point the hand held printer I/R LED directly at the DPC-12 or DPC-24 control

module I/R LED within 3 ft (1m).

Press EXECUTE to enter the menu.

Press MENU ( ) to scroll through and select which item(s) to printout.

SYSTEM?

Prints general system information and configuration settings.

V-LIMIT?

Prints the output voltage limit settings for each of the 12 or 24 dimmer outputs.

CURVES?

Prints the dimmer curves for all 12 or 24 dimmer outputs.

Ø-PATCH?

Prints the phase patch for all 12 or 24 dimmer outputs.

DCPATCH?

Prints the configuration settings for the dimmer to channel patch.

SCENE>FL

Press MENU ( ) to select the desired scene (01 to 12 or 24) or all scenes (FL).

SCENE?

Prints the level settings for each dimmer output within the 12 or 24 scenes.

SCENE>01

Press EXECUTE to toggle the pointer (>) and select which scene to print.

FD-TIME?

Prints the fade time settings for each of the 12 or 24 scenes.

2 ROOM?

Prints the two room assignment for each of the 12 or 24 dimmer outputs.

ALL?

Printout all items at once.

PRINTING

Press EXECUTE on any item to begin printing.

Press ESCAPE or RESET to exit the menu.