Technical data, Rated data supply modules – Lenze i700 Manual User Manual

Page 35

Advertising
background image

Technical data

Rated data

Supply modules

4

l

35

EDS700ACBA EN 4.0

Fuses and cable cross−sections

Operation with external mains choke/mains filter

Type

Installation according to EN 60204−1

1)

Installation according to UL

2)

FI

3)



‚

L1, L2, L3 − Laying system



ƒ

L1, L2, L3

B2

C

F

[A]

[A]

[mm

2

]

[mm

2

]

[mm

2

]

[A]

[A]

[AWG]

[mA]

E70ACPSx0304x

C40

40

10

6

40

40

8

³ 300

E70ACPSx0604x

C63

63

16

10

60

6

³ 300

1)

The data are recommendations. Other designs/laying systems are possible (e.g. in accordance with VDE 0298−4). The
cable cross−sections apply under the following conditions: use of PVC−insulated copper cables, conductor
temperature < 70 °C, ambient temperature < 45°C, no cable or core bundling, three loaded cores.

2)

Only use UL−approved cables, fuses, and fuse holders.
UL fuse: voltage

³ 500 V, tripping characteristic "J", "T", or "G". The cable cross−sections apply under the following

conditions: conductor temperature < 75 °C, ambient temperature < 45°C.

3)

Universal−current sensitive earth−leakage circuit breaker, short−time delayed, type B
In the case of cable lengths > 50m, depending on the cable type and the switching frequency, the circuit−breaker
may respond.

 Circuit breaker

‚ Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category

ƒ Fuse
Observe national and regional regulations