5 technical data, 1 general data, Technical data – Lenze CANopen Controller-based Automation User Manual

Page 20: General data, 5technical data

Advertising
background image

Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17

20

5

Technical data

5.1

General data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5

Technical data

5.1

General data

Area

Values

Communication profile

CANopen (DS301, V4.02)

Standards

CAN, ISO 11898 / EN 50325-4

Network topology

Line, terminated at both ends with 120 

(e.g. terminated with Sub-D plug of type EWZ0046)

Max. number of nodes

127

Adjustable node addresses

1 ... 127

(adjustable for Lenze devices via DIP switches)

Baud rates [kbps]

• 10

• 20

• 50

• 125

• 250

• 500

• 1000

Parameter data

Max. 10 client and server SDO channels with 1 ... 8 bytes

Cycle time - Motion/CNC task

1 ... 16 ms

Number of drives/ms on the Motion

bus

Max. 3 drives/ms

Signal propagation delay drive



controller



drive

4 cycles

Cross communication

Only possible with CANopen (Logic)

In the case of CANopen (Motion), communication is executed centrally via

the Lenze Controller.

Number of DI + DO (bits/ms)

384 (max. 6 PDOs/ms on the Logic bus)

Cycle synchronisation with locked

PLL (Jitter)

+/-10 μs

Advertising