Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17

22

5

Technical data

5.4

Bus cable length

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.4

Bus cable length

5.4.1

Total cable length

The total cable length is also specified by the baud rate.

5.4.2

Segment cable length

Repeaters divide the total cable length into segments. The segment cable length is defined by the

cable cross-section and the number of nodes per segment. Without a repeater, the segment cable

length corresponds to the total cable length.

Note!

• It is absolutely necessary to comply with the permissible cable lengths.
• Observe the reduction of the total cable length due to the signal delay of the repeater.

Use of repeaters

( 23)

• If the total cable lengths of the nodes are different at the same baud rate, the smaller

value must be used to determine the max. cable length.

Baud rate [kbps]

Max. bus length [m]
Servo Drives

9400

Inverter Drives

8400

I/O-System 1000

(EPM-Sxxx)

CANopen bus coupler

10

8000

-

5000

20

4000

-

2500

50

1500

1500

1000

125

600

600

500

250

275

275

250

500

110

110

80

1000

13

13

25

Max. number of

nodes per segment

Cable cross-section

0.25 mm

2

0.50 mm

2

0.75 mm

2

1.00 mm

2

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

100

150 m

270 m

410 m

600 m