HUMIDITY TRANSDUCER SPECIFICATIONS

Accuracy*: ± 2% / ±3% RH
Range: 0-100% RH
Hysteresis: ± 1%
Supply Voltage: 12-40 VDC

12-35 VAC (VDC output units only)
Compensated Temp Range: -30°F to 130°F (-35°C to 55°C)
Load Impedance: 1.5K ohms max. at 40 VDC (mA output units)

1K ohms min. (VDC output units)

* Includes non-linearilty and non-repeatability

Inspection

Requirements

For Additional Information See HU-226 Data Sheet

INSTALLATION

8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA

800-843-5116 • 952-556-4900 • Fax 952-556-4997

[email protected] • www.mamacsys.com

Model HU-226

Technical Information

TI.226-05

HUMIDITY / TEMP SENSOR

Inspect the package for damage. If damaged, notify the appropriate

carrier immediately. If undamaged, open the package and inspect

the device for obvious damage. Return damaged products.

Do not use on oxygen service, in an explosive/hazardous

environment, or with flammable/combustible media.

Disconnect power supply before installation to prevent

electrical shock and equipment damage.

Make all connections in accordance with the job wiring diagram

and in accordance with national and local electrical codes. Use

copper conductors only.

Use electrostatic discharge precautions (e.g., use of wrist straps)

during installation and wiring to prevent equipment damage.

Avoid locations where severe shock or vibration, excessive

moisture or corrosive fumes are present. NEMA Type 4 housings

are intended for outdoor use primarily to provide a degree of

protection against wind-blown dust, rain, and hose-directed water.

Do not exceed ratings of the device.

Tools (not provided)

- Digital Volt-ohm Meter (DVM)

- Appropriate screwdriver for mounting screws

- Appropriate drill and drill bit for mounting screws

Appropriate accessories

Two #8 self-tapping mounting screws (not provided)

Training: Installer must be a qualified, experienced technician

RoHS

HU-226

Duct Mount

THERMISTOR SENSOR SPECIFICATIONS

Interchangeability: ± 0.2°C
Heat Dissipation: 3.0 mW/°C
R/T Characteristics: Refer to TI.700-11 (See Temperature Sensor section)
Operating Temp Range: -30°F to 130°F (-35°C to 55°C)

PLATINUM RTD SENSOR SPECIFICATIONS

Accuracy: 0.12% at 0°C
Resistance: 100 or 1,000 ohm at 0°C
Standard: DIN 43760
Heat Dissipation: 3.0 mW/°C
R/T Characteristics: Refer to TI.700-11 (See Temperature Sensor section)

GENERAL SPECIFICATIONS

CONFORMANCE & TESTING

Environmental: 10-90%RH Non-Condensing
Enclosure: 18 Ga C.R. Steel NEMA 4 (IP-65)
Finish: Baked on enamel - PMS2GR88B
Termination: Unpluggable screw terminal block
Wire Size: 12 Ga maximum
Weight: Duct Mount: 1.0 lbs. (.45 kg)

TEMP SENSOR

ACCURACY

(4-20 mA 2-wire)

(0-5 VDC/0-10 VDC

field selectable)

mA

VDC

Ex: HU-226-2-mA-3 - Humidity/Temp

Sensor, ±2%RH accuracy with 4-20 mA

output and 1,000-ohm Platinum RTD.

OUTPUT

±

2%

ORDERING INFORMATION - HU-226-

±

3%

1

2

3

4

5

7

8

10

12

13

14

15

16

17

18

21

100 ohm Platinum RTD
1,000 ohm Nickel RTD

(5,000 PPM)
1,000 ohm Platinum RTD

1,000 ohm Nickel RTD

(6,000 PPM)

1,000 ohm Balco RTD

10,000 ohm NTC Thermistor

(Type III)

10,000 ohm NTC Thermistor

(Carel)

3,000 ohm NTC Thermistor

10,000 ohm NTC Thermistor

(Type II)

5,000 ohm NTC Thermistor

1,035 ohm Silicon PTC

100,000 ohm NTC

10,000 ohm NTC Thermistor

(Eliwell)

Thermistor

20,000 ohm NTC Thermistor

2,252 ohm NTC Thermistor

1,800 ohm NTC Thermistor

Operating Temp Range: -30°F to 130°F (-35°C to 55°C)

Warning:

Caution:

RoHS Compliant

EMC Testing: BS EN 55022:1998, BS EN 55024:1998,

EN 61000-3-3, EN 61000-4-2,

EN 61000-4-3, EN 61000-4-4,

EN 61000-4-5, EN 61000-4-6

EN 61000-4-11

For Resistance vs. Temperature Tables,

please refer to TI.700.11