Ti.226-05_pg3, Rohs, Vdc output – MAMAC Systems HU-226 User Manual

Page 3: Model hu-226, Technical information, Humidity / temp sensor, Page 3 of 4, Z s temp

Advertising
background image

Model HU-226

Technical Information

TI.226-05

HUMIDITY / TEMP SENSOR

Page 3 of 4

RoHS

TYPICAL APPLICATIONS (wiring diagrams)

Neutral

Hot

+

Controller / Meter / Recorder

VDC Output Transducer Only

12-35 VAC Transformer

Figures 3 & 4 illustrate typical wiring diagrams for the HU-226, 0-5/0-10

VDC output humidity transducers.

Figure 3 - Wiring for VDC Output when applied with External AC Supply

Figure 4 - Wiring for VDC Output when applied with External DC Power

Supply

Signal

+

Common

Supply

O

+

Controller / Meter / Recorder

VDC Output Transducer Only

12-40 VDC Power Supply

HU-226 humidity transducers with VDC output are field selectable 0-5 VDC or
0-10 VDC output and can be powered with either 12-40 VDC or 12-35 VAC.

The following describes the proper wiring of these humidity transducers with
VDC output:

Wiring HU-226 Units with VDC Output

0 to 10 VDC

(Factory Default)

0 to 5 VDC

HU-226 Humidity Transducer with VDC Output

Figure 5 - Dip Switch Settings for HU-226 VDC Output

VDC Output

+ - 0

ON

1

2

Z S

temp

HUMIDITY SENSOR:
1. Remove the terminal block by carefully pulling it off the circuit board.
2. Locate the [+], [-] and [O] terminal markings on the board.
3. Attach the power wires to the [+] and [-] terminals. The [-] terminal is

also the negative output terminal.

4. Connect the [O] terminal, which is the positive VDC output terminal, to

the controller’s input terminal.

5. Re-insert the terminal block to the circuit board and apply power to the

unit.

6. Check the appropriate VDC output using a voltmeter set on DC volts

across the [O] and [-] terminals.

TEMP SENSOR:
1. Remove the terminal block by carefully pulling it off the circuit board.
2. Use shielded 18-22 AWG wire to connect temp sensor as shown in

Figures 3 & 4.

Input Signal

+

Common
Shield/Ground

Temp
Input

Input Signal

+

Common
Shield/Ground

Temp
Input

Humidity

Temp

Signal

+

Common

Supply

O

Humidity

Temp

HU-226

DUCT MOUNT

0 to 10 VDC (default)

0 to 5 VDC

1

2

O N

1

2

O N

Advertising