Ti.226-05_pg2, Rohs, Ma output – MAMAC Systems HU-226 User Manual

Page 2: Model hu-226, Technical information, Humidity / temp sensor, Page 2 of 4

Advertising
background image

Model HU-226

Technical Information

TI.226-05

HUMIDITY / TEMP SENSOR

Page 2 of 4

TYPICAL APPLICATIONS (wiring diagrams)

HU-226 humidity transducers are 4-20 mA output units powered with a
12-40 VDC supply.

The following describes the proper wiring of these humidity and temp sensors
with mA output:

HUMIDITY SENSOR:
1. Remove the terminal block by carefully pulling it off the circuit board.
2. Locate the [+] and [-] terminal markings on the board.
3. Attach the supply voltage to the [+] lead.
4. Connect the 4-20 mA output ([-] terminal) to the controller’s input terminal.
5. Ensure that the power supply common is attached to the common bus of

the controller.

6. Re-insert the terminal block to the circuit board and apply power to the unit.
7. Check for the appropriate output signal using a DVM set on DC milliamps

connected in series with the [-] terminal.

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12-40 VDC Power Supply

+

Controller / Meter / Recorder

mA Output Transducer Only

Figures 1 & 2 illustrate typical wiring diagrams for the HU-226, 4-20 mA,

two-wire humidity transducers.

Figure 1 - Wiring for mA Output Humidity Transducer with External DC

Power Supply

Figure 2 - Wiring for mA Output HumidityTransducer where Controller or

Meter has Internal DC Power Supply

RoHS

Mounting

HU-226 (DUCT) - Refer to Figure 6 for mounting dimensions.

1. Drill 5/8” hole in appropriate location.

2. Mount transducer on a vertical surface with two #8

self-tapping screws (not provided).

3. Pull wires through knockout and make necessary connec-

tions (see wiring diagrams).

4. Replace cover and tighten Philips screws.

Wiring

Use maximum 12 AWG wire for wiring terminals. Refer to

Figures 1, 2, 3, & 4 for wiring information and Figure 5 for dip

switch designations.

Wiring HU-226 Units with mA Output

HU-226 Humidity Transducer with mA Output

Caution: If you are using grounded AC, the hot wire must be on

the [+] terminal. Also, if you are using a controller without built-in
isolation, use an isolation transformer to supply the HU-226
transducer.

Caution: This product contains a half-wave rectifier power

supply and must not be powered off transformers used to power
other devices utilizing non-isolated full-wave rectifier power
supplies.

Caution: When multiple units are powered from the same

transformer, damage will result unless all 24G power leads are
connected to the same power lead on all devices. It is manda-
tory that correct phasing be maintained when powering more
than one device from a single transformer.

mA Output

TEMP SENSOR:
1. Remove the terminal block by carefully pulling it off the circuit board.
2. Use shielded 18-22 AWG wire to connect temp sensor as shown in

Figures 1 & 2.

Humidity

Temp

Temp
Input

Humidity

Temp

Input Signal

+

Common
Shield/Ground

Temp
Input