In all loop diagnostic modes, AC voltage is displayed. If more than 2 VAC is present on the Model 532’s

terminals, the display is highlighted to alert the user of a potential problem.

In all loop diagnostic modes, HARTâ activity is indicated with “© HART DETECTED ©” . The © symbols

flash on and off with the actual HARTâ messages.

J.

Modes of Operation

Read Milliamp

Connect the Model 532 in series with

the process loop to monitor current.

Observe correct polarity. Current

limiting above 24.000 mA is indicated

by a flashing “CURRENT LIMITED”

display.

Power and Measure 2 Wire Transmitter

The Model 532 provides power to the process

loop while displaying output current. Use this

mode to test a transmitter’s ability to control

loop current. Current limiting above 24.000

mA is indicated by a flashing “CURRENT

LIMITED” display.

Read Volts

The Model 532 measures +/- 30 VDC with 4X

overrange ability. The display flashes

“OVERRANGE” when the 30 volt limit is

exceeded. 0.001 volt resolution below 24.00

volts provides the ability to calibrate 1-5 volt

instrumentation.