Table 2: R-value Recommendations by Climate Zone for each enclosure element

Climate
Zone

Wall

Vented
Attic

Compact
Roof

Basement
Wall

Exposed
floor

Slab
edge

1

Windows
(U/SHGC)

Sub-slab

2

1

10

40

35

5

10

none

yes

none

2

15

50

40

10

20

5

0.35/<0.25

none

3

20

50

45

10

20

7.5

0.30/<0.3

5

4

25

60

45

15

30

7.5

0.30/<0.35

7.5

5

30

65

50

15

30

10

0.24/<0.50

7.5

6

35

75

60

20

40

10

0.18/--

10

7

40

90

65

25

45

15

0.15/--

15

8

50

100

75

35

50

20

0.15/--

20

Table 3: ROXUL COMFORTBOARD IS Thickness to Reach Recommended R-value for Various Wall Assemblies

Nominal

R-value

Wall Assemblies with ROXUL® COMFORTBOARD™ IS Thickness

2x6 wood frame with R-

22 COMFORTBATT

2x4 wood frame with
R14 COMFORTBATT

Load bearing clay

masonry or CMU

10

-

-

3”

15

-

1”

4”

(2+2)

20

-

1.5”

5”

(2+3)

25

1”

3”

7”

(3+4)*

30

2”

4”

(2+2)

8”

(4+4)*

35

4”

(2+2)

6”

(3+3)

9”

(6+3)*

40

5”

(2+3)

7”

(4+3)*

10”

(6+4)*

50

7”

(4+3)*

9”

(6+3)*

12”

(6+6)*

* Values in parentheses give the thicknesses of each layer of insulating sheathing required to make up the
total thickness. For example, (6+6) would be two layers of 6” thick insulating sheathing to make a total of
12”. Standard available thicknesses may vary – please consult

www.ROXUL.com

or contact sales for

details.

CMU = Concrete Masonry Unit