iv. vapor permeable “peel and stick” self-adhered membrane

v. vapor impermeable membranes may be used depending on vapor control design (see Section 06 below)

04.

AIR CONTROL LAYER

a.

The drainage plane may be detailed as the primary air control layer if made continuous.

b.

If an air permeable cavity insulation is selected an airtight drywall approach should be used. An airtight drywall
approach requires all penetrations of the gypsum board to be carefully sealed.

c.

Multiple planes of airtightness are recommended where practical to control convection within the enclosure cavity.

05.

THERMAL CONTROL LAYER

a.

ROXUL COMFORTBOARD IS insulation is the primary thermal control layer.

b.

The amount of insulation recommended varies by climate region (see

Table 2

)

06.

VAPOR CONTROL LAYER

a.

The assembly as illustrated is a “vapor open” assembly, meaning that there is a single line of vapor control and that
drying can occur towards the interior or towards the exterior from this line. Selection of vapor-open interior finishes
should be considered. If vapor impermeable finishes are used, analysis should be conducted to assess drying
potential.

07.

EXTERIOR CLADDING

a.

A drained and back-ventilated wood or fiber cement siding is illustrated.

b.

Material options for the exterior cladding include:

i. Vinyl siding (see manufacturer’s notes for installation on furring)

ii. Wood siding

iii. Fiber cement siding or panels

08.

QUALITY CONTROL CONSIDERATIONS

a.

Inspect the lapping of drainage plane pieces to ensure that pieces are installed in “shingle” fashion.

b.

Ensure a tight fit where the exterior insulation boards are fit together. At mechanical and structural penetrations, an
opening in the ROXUL COMFORTBOARD IS layer may be cut slightly undersized to ensure a tight fit.