‎Chapter 5 Configuring the PM135

General Meter Setup

PM135 Powermeter Series

81

Device Options

The Device Options setup allows changing user-configurable device
options or putting the meter into energy test mode.

Using the Front Display

Select Device Options from the Device Setup menu. See

Viewing and

Changing Setup Options

in Chapter 3 for information on configuring

parameters via the front display.

Device Setup

Reset
Real Time Clock
Display Setup
Basic Setup

Device Options

COM1 Setup
COM2 Setup

Using PAS

Select General Setup from the Meter Setup menu, and then click on the
Device Options tab.

Table 10 lists available device options.

Table 10: User-configurable Device Options

Parameter

Options

Default

Description

Power Calculation

Mode

Reac = using reactive

power S=f(P, Q),

Nact = using non-active

power Q=f(S, P)

S=f(P, Q) The method used for

calculating reactive and

apparent powers (see

Power

Calculation Modes

below)

Energy Roll Value

E, EH

10000 kWh
100000 kWh

1000000 kWh

10000000 kWh

100000000 kWh

1000000000 kWh

10000000 The value at which energy

counters roll over to zero

Phase Energy
Calculation

E, EH

Disabled

Enabled

Disabled

Enables phase energy

calculations

Energy Test Mode

E, EH

Disabled

Wh pulses

varh pulses

Disabled

Setting this option puts the

meter into the energy test

mode (see

Energy Pulse LED

in Chapter 3)

Starting Voltage

1.5-5.0%

1.5%

The device starting voltage in
percent of FS (120V or 400V)

Device Resolution

Low

High

Low

The voltage, current and

power resolution on the front

display (see

Measurement Units

in Chapter 3) and in

communications (see

communication guides)

Volts Scale, V

60-828 V

144 V

The maximum voltage scale

allowed, in secondary volts.

See

Data Scales

in Appendix F