Communicating via the internet, Input and output ratings – SATEC PTS175 Quick Start User Manual

Page 13

Advertising
background image

PM175 Quick Start Guide

Communicating via the Internet
If you are communicating through the Ethernet port, define the IP address of your

meter on the network.
To define the IP address:

1. On the Instrument Setup tab, select Internet Site.
2. Click on the Connection tab.
3. Select the IP Address and type in the IP address of your meter.

The default IP address preset at the factory is 192.168.0.203.

4. In the Protocol box, select the communications protocol for the

TCP port. The meter can provide Modbus/TCP connections on

TCP port 502 and DNP3/TCP connections on port 20000. The

host port is set automatically as you select the protocol. Select

Modbus RTU for Modbus/TCP or DNP3 for DNP3/TCP.

5. In the Wait for Answer box, adjust the time that PAS waits for a

connection before announcing an error and the number of

retries PAS uses to receive a response from the device if

communications fail.

Input and Output Ratings

3 voltage inputs

690 V: (standard)

DIRECT INPUT - Nominal: 690V line-to-line voltage,

790V maximum; 400V line-to-neutral, 460V maximum -

Burden: <0.4 VA. INPUT USING PT - Burden: <0.15 VA

120 V: (optional)

INPUT USING PT - Nominal: 120V line-to-line voltage,

144V maximum - Burden: <0.04 VA

Voltage input terminals Maximum wire section: 4 mm2 (10 AWG)

3 current inputs
(Galvanically

isolated)

5A: (standard)

INPUT VIA CT with 5A secondary output - Burden: 2.5 to

4 mm2 (13-11 AWG) wire from CT.
Operating range: continuous 10A RMS Burden: < 0.1 VA
Overload withstand: 15A RMS continuous, 10A RMS for

1 second.

1A:(optional)

INPUT VIA CT with 1A secondary output - Burden: 2.5 to

4 mm2 (13-11 AWG) wire from CT.
Operating range: continuous 2A RMS Burden: < 0.02 VA
Overload withstand: 3A RMS continuous, 80A RMS for 1

second.

Communication

port COM1

EIA RS-485 standard

Optically isolated, max. speed 115.2Kb/s

COM1 terminals

3 x Maximum wire section: 2.5 mm2 (12 AWG)

Communication

port COM1

(Optional)

Profibus

Max. speed 12 Mb/s

Profibus terminals

5 x Maximum wire section: 2.5 mm2 (12 AWG) or using

terminal to DB9 converter: P/N AC0153 REV.A2

Communication

port COM2

(Optional)

Ethernet

10/100 Base T, auto adaptation speed,

Max. speed 100Mb/s

ETH connector

Shielded RJ45 cable

Power Supply
(Galvanically

isolated)

120/230 V AC/DC

(standard)

85-265VAC, 88-290VDC; 50/60/400 Hz 9VA

12 VDC (optional)

9.5-18 VDC

24/48 VDC (optional)

18.5-72 VDC

Power Supply input

terminals

3 x Maximum wire section: 2.5 to 4 mm2

(13-11 AWG)

BG0456 REV.A2

13