Bosch AQUA STAR 2400E LP User Manual

Page 31

Advertising
background image

6 720 608 263

Maintenance and service

31

Fig. 43 Adjusting P2 CO

2

level

3. Verify both P1 and P2 CO

2

readings are within the

ranges specified in table 10. Repeat steps 1 and 2 as
necesssary until CO

2

values are within the specified

ranges.

4. Once CO

2

values are within the specified ranges,

verify the CO readings on P1 do not exceed 300ppm
(follow local codes). If values exceed this limit, inspect
vent system and fin coils (Chapter 5.1) for blockage.

D. Returning to Service:

1. Return slotted screw cover to original position.
2. Reinstall Torx cover.
3. Remove CO

2

analyzer probe and reinstall flathead

screw with gasket in exhaust collar.
4. Install front cover.
5. Turn ON/OFF switch to the OFF (O) position and
then back to the ON (I) position.
6. Heater is ready for normal operation.

Final Readings

P2 CO

2

Reading:

% CO

2

P1 CO

2

Reading:

% CO

2

CO

2

level

Max CO

level

Nat. Gas

max. input

P1

9.7 ± 0.3 %

300 ppm

min. input

P2

9.5 ± 0.5 %

LP Gas

max. input

P1

10.7 ± 0.3 %

300 ppm

min. input

P2

10.5 ± 0.5 %

* Final reading must be confirmed with the front cover on,
CO

2

levels increase when the cover is installed.

Table 10