Thrush co – Thrush Pressurizer-VS PB-VSI Series User Manual

Page 16

Advertising
background image

Section 6

Electrical Drawings


6.1 Electrical Drawings (for use with ABB Drive)

Before installation and or servicing electricity to the VFD, refer to the ABB user

manual supplied with the Pressurizer-VS for all safety warnings and cautions.

The figures in this section illustrate factory wiring for reference in the event a component
or the wiring needs replaced on the Pressurizer-VS. Figure 6-1-1 illustrates incoming
power and ground connections to the VFD. Figure 6-1-2 motor to VFD, 6-1-3 low-
pressure switch to VFD, and 6-1-4 pressure transmitter to VFD.

ABB TERMINAL

VOLTAGE

MOTOR

ABB GROUND

ABB GROUND

MOTOR GROUND
(CONDUIT BOX)

ABB TERMINAL

INCOMING POWER AND GROUND

NOTE: USE U1, V1, AND W1 FOR 3 PHASE.
USE U1 AND V1 FOR 208-240 SINGLE PHASE.

U1/L

V1/N

W1

U2

V2

W2

1

3

2

1‐7

3‐9

2‐8

460V 3PH

208‐230V 3PH

4‐7/5‐8/6‐9

4‐5‐6

Figure

6-1-1

Figure

6-1-2


Pressure Transmitter

Low-Suction Switch

5 ON DRIVE

9 ON DRIVE

14 ON DRIVE

JUMPER
9 TO 13

JUMPER

10 TO 11

1
2
34

00HN7

ZE

RO

R1
1

SPAN

ZE

R

O

MEN

U

LE

D

CO
N

N

Figure

6-1-3

Figure 6-1-4

Thrush Co.

Manual #9636-1400

12