6.2 Electrical Drawings (for use with Yaskawa Drive)

Before installation and or servicing electricity to the VFD, refer to the Yaskawa

user manual supplied with the Pressurizer-VS for all safety warnings and cautions.

The figures in this section illustrate factory wiring for reference in the event a component
or the wiring needs replaced on the Pressurizer-VS. Figure 6-2-1 illustrates incoming
power and ground connections to the VFD. Figure 6-2-2 motor to VFD, 6-2-3 low-
pressure switch to VFD, and 6-2-4 pressure transmitter to VFD.

YASKAWA TERMINAL

VOLTAGE

MOTOR

YASKAWA
GROUND

YASKAWA
GROUND

MOTOR GROUND
(CONDUIT BOX)

YASKAWA TERMINAL

INCOMING POWER AND GROUND

NOTE: USE L1, L2, AND L3 FOR 3 PHASE.
USE L1 AND L2 FOR 208-240 SINGLE PHASE.

R/L1

S/L2

TL3

U/T1

V/T2

W/T3

1

3

2

1‐7

3‐9

2‐8

460V 3PH

208‐230V 3PH

4‐7/5‐8/6‐9

4‐5‐6

Figure

6-2-1

Figure

6-2-2

Pressure Transmitter

Low-Suction Switch

A2 ON DRIVE

V+ ON DRIVE

S3 ON DRIVE

12

34

00HN

7

ZER

O

R1
1

SPA

N

ZE

R

O

ME
N

U

LE

D

CON

N

SN ON DRIVE

Figure 6-2-3

Figure 6-2-4

Thrush Co.

Manual #9636-1400

13