The Radio Path Test feature should not be enabled on a live system; it is intended for testing only.

RSSI Test

The first test (RSSI Test) uses the RS232, LED to indicate the RSSI level from the Access Point. The LED will be green
when the RSSI to the Access Point is greater than the configured RSSI Strong Threshold or red when the RSSI to the AP
is greater than the configured RSSI Weak Threshold. If the RSSI to the AP is less than the RSSI Weak Threshold then the
RS232 LED will be off.

When the Radio Path Test is enabled, the OK LED will flash alternately between green and red indicating that it is in a
diagnostic mode.

Throughput Test

The second test is the Throughput Test which when enabled performs a basic throughput test between the AP and Client.
The configurable Remote Device IP Address should specify the IP Address of the AP

Note that the onboard iperf server must be enabled at the AP prior to running this test.

The Throughput Test will run through a continuous cycle where data is transferred for 10 seconds, followed by 10
seconds of silence. The RS485 LED and the DIO LED are used as indicators of the throughput test. While data is being
transferred the DIO LED will be red, and while no data is being transferred the DIO LED will be off.

If the average throughput over the 10 second duration of the throughput test is greater than the configurable Throughput
High Threshold, then the RS485 LED will be green; otherwise if the throughput is greater than the configurable
Throughput Low Threshold then the RS485 LED will be red; if the measured throughput is less than the Throughput Low
Threshold then the RS485 LED will be off.

Radio Path Test

can be accesses by selecting the link from the “System Tools” page and then ticking the “Enable Radio

Path Test” and entering in appropriate thresholds levels to indicate RSSI and Throughput and the IP address of the Iperf
Server (normally the Access Point).

The following screen shot shows the indications you will see using the Configuration above.

The OK Led will flash between Red and Green which indicates the module is in a diagnostic Radio Test Mode.

RS-232 Led is showing a green indication which means the RSSI to the Access Point is greater than -40dB. If the RS232
Led showed Red it would indicate the RSSI level was greater than -60dB.

Radio Path Test Settings

Enable Radio Path Test

Enables or disables the Radio Path Test.

RSSI Strong Threshold

Strong RSSI indication threshold

RSSI Weak Threshold

Weak RSSI indication threshold

Enable Throughput Test

Enables or disables the Throughput test (independent of Radio Path
Test (RSSI)

Remote Device IP
Address

IP Address of the Remote device that you wish to path test

Throughput High
Threshold

High Throughput indication value. Generally configured with the
desired throughput level

Throughput Low
Threshold

Low Throughput indication value.