Factory boot” switch, Usb host port, Dipswitches – Weidmuller WI-I/O-9-U2: Wireless Mesh I/O & Gateway User Manual V1.2.2 User Manual

Page 29

Advertising
background image

28

“Factory Boot” switch

The “Factory Boot” switch is used for factory setup and diagnostics. This switch should
not normally be used, except if advised by WEIDMULLER support.

USB Host port

This port is a USB Host (Master port), which can interface with USB storage devices for
data logging (Future) and for upgrading the module Firmware

– See section 4.4.7

“System Tools” for details on how this is done.

Dipswitches

The Dipswitches are used to select a number of functions within the module; the table
below indicates the different switch positions.

Dipswitches 1 to 2

– Selection for measuring Current or Voltage on Analog Input

3. Set DIP switches ON to measure Current (0-20mA) and OFF for Voltage (0-
5VDC).

Dipswitches 3 to 4

– Selection for measuring Current or Voltage on Analog Input

4. Set DIP switches ON to measure Current (0-20mA) and OFF for Voltage (0-
5VDC).

Dipswitch 5

– DIP Switch not used

Dipswitch 6

– When set to ON (Enabled) and the module is restarted; it will boot

up with a known factory default configuration including a default IP address for
Ethernet connection. (Refer to Chapter 4 -

“Default IP Address”).

Note: When dipswitch is ON, Radio and I/O functionality is disabled.


Switch

Function

Current

Voltage

DIP 1 & 2

Analog Input #3

DIP 3 & 4

Analog Input #4

Switch

Function

Disabled

Enabled

DIP 5

Not used

DIP 6

Setup Mode