4 digital outputs (pulsed outputs), Digital output fail safe status, Figure 14 – Weidmuller WI-I/O-9-U2: Wireless Mesh I/O & Gateway User Manual V1.2.2 User Manual

Page 32: Digital output wiring

Advertising
background image

31

2.5.4 Digital Outputs (Pulsed Outputs)

Digital outputs are open-collector transistors and are able to switch loads up to 30VDC,
200mA.

The 8 digital outputs share the same terminals as the digital input. These terminals are
marked D1-8.

Figure 14

– Digital Output Wiring

When active, the digital outputs provide a transistor switch to EARTH (Common).

To connect a digital output, refer to

“Figure 14” above. A bypass diode (IN4004) is

recommended to protect against switching surges for inductive loads such as relay
coils.

The digital channels D1-4 on the WI-I/O 9-U2 module can be used as pulse outputs with
a maximum output frequency of 10 KHz.

Digital Output Fail Safe Status

As well as indicating the Digital Output status (on / off), the LEDs can also indicate a
communications failure by flashing the Output LED. This feature can be utilised by
configuring a Fail Safe time and status on the “I/O – digital Output” screen in the
Configuration software as shown below.

WI-IO 9-U2

Advertising