Specifications – Rockwell Automation 13DJ3 Liquid Level Controls User Manual

Page 3

Advertising
background image

3

Table 1: Level and Resistance Control

Specifications

Power Consumption:

3 watts (includes control base)

Resistivity Range:

Typical liquid resistivity 0--60 MegOhms • centimeter
(See Table 5)

Resistance Sensing Sensitivity:

0--15 MegOhms in six ranges. (See Table 6, Consult factory for higher ranges.)

Maximum Probe Voltage:

22.5V AC (Ranges 1, 2, & 3), 29 VAC (Ranges 4, 5, & 6) (See Table 6)

Maximum Probe Current:

65 mA to 0.001 mA. (See Table 6)

Solid State Output Signal:

12V DC open circuit limited to 30mA short circuit. Terminals #5 and #2 on Control Base.

Speed of Response:

0.003 sec. to 0.20 sec. (See Table 7)

Permissible Lead Length:

Up to 2,000 ft (609.6 m) (See Table 8) Use #16 AWG wire minimum

Ambient Temperature:

--40 to 135°F (--40 to 57°C)

Bulletin Number

Control Base

Output

Voltage Supply

Output Characteristics

Response Time

Resistivity Range

Type

Rating

Leakage

13DJ3-3000

Refer to Table 7

Refer to Table 6

60-1600B

120V AC

50/60 Hz

60-1601B

240V AC

50/60 Hz

8-670
supplied with
control base

DPDT

EM

Relay

5A, 120V AC

2.5A, 240V AC

1A, 120V DC

8-651

SPNO

TRIAC AC

1A, 265V AC

20mA min.

1mA

8-652

SPNO

FET AC/DC

30mA,

120V AC/DC

10μA

63-116

Voltage

DC Output

30mA,

24V DC

63-115

NPN Open

Collector

250mA,

24V DC

1mA

Advertising