7

Table 5: Typical Control Ranges and Probe Materials (continued)

Measured at normal room temperature

Suitable probe materials

SS = 316 stainless steel (standard)
M = Monel
HB = Hastelloy B2
HC = Hastelloy C

Table 6: Level and Resistance Sensing Ranges

Note: All range resistors are 1/2 W ±

10% except Range 1, which is 2 W.

Typical Liquid

Concentration

(% by weight)

Resistivity Range

(ohms cm)

Control Range

Suitable Probe

Material

Potassium Sulfide

5--50

2--10

1

SS

Propionic Acid

5--30

900--1,200

2

M

Refrigerants

2MΩ--20MΩ

5 or 6

SS

Silver Nitrate

10--60

5--20

1

SS

Sodium Acetate

20--30

15--18

1

SS

Sodium Carbonate

5--15

10--20

1

SS

Sodium Chloride

5--25

5--15

1

SS

Sodium Hydroxide

20--50

5--20

1

M

Sodium Iodide

10--40

5--20

1

SS

Sodium Nitrate

10--30

7--12

1

SS

Sodium Sulfate

10--15

8--12

1

SS

Sodium Sulfide

2--18

5--20

1

SS

Strontium Chloride

10--20

5--12

1

SS

Strontium Nitrate

10--40

10--15

1

SS

Sulfuric Acid

5--50

1--10

1

HC

Synthetic Latex

2MΩ--20MΩ

6

SS

Tapwater

2,000--20,000

3

SS

Zinc Chloride

10--40

10--15

1

M

Zinc Sulfate

5--30

20--100

1

SS

Range

Liquid Resistivity

ohms/cm

Resistance

Sensing

Range

Resistor

Maximum

Volts

Maximum

Current

Typical

Solutions

1

0 -- 600

0 -- 150Ω

Orange
Orange
Brown

330Ω

22.5 V AC

65 mA

Acids Bases Salts

2

600 -- 6,000

150 -- 1,500Ω

Red
Violet
Red

2,700Ω

22.5 V AC

8.33 mA

Beer Milk Water

3

6,000 -- 60,000

1,500 -- 15,000Ω

Red
Violet
Orange

27,000Ω

22.5 V AC

0.83 mA

Water Alcohols Distilled
Water

4

60,000 -- 0.6MΩ

15,000 -- 150,000Ω

Red
Violet
Yellow

270,000Ω

29 V DC

0.1 mA

Alcohols Ammonia Distilled
Water

5

.6MΩ -- 6MΩ

150,000 -- 1.5MΩ

Red
Violet
Green

2.7MΩ

29 V DC

0.01 mA

Antibiotics
Refrigerants

6

6MΩ -- 60MΩ

1.5 -- 15MΩ

Red
Violet
Blue

27MΩ

29 V DC

0.001 mA

Refrigerants
Synthetic Latex

Advertising