Ordering instructions, Installation, Mounting – Rockwell Automation 13DJ3 Liquid Level Controls User Manual

Page 8

Advertising
background image

8

Table 7: Speed of Response (seconds)

Ordering Instructions

1. Select 13DJ3--3000

2. Select Control Base

3. Select Probe Fitting

4. Select Probe Rod Assemblies for 61 Series Probe Fittings

Range

Solid-State Outputs

Relay Output

ON

OFF

ON

OFF

1

0.003

0.060

0.012

0.070

2

0.0035

0.060

0.013

0.070

3

0.004

0.060

0.014

0.070

4

0.006

0.060

0.018

0.070

5

0.023

0.060

0.033

0.070

6

0.190

0.190

0.200

0.200

Bulletin Numbers

Voltage Supply

Description

60- 1600B

120 VAC

50/60 Hz

Open Type

60- 1610B

NEMA 1 Enclosure

60- 1601B

230 VAC

50/60 Hz

Open Type

60- 1611B

NEMA 1 Enclosure

For NEMA 3, 4, 12, and 13; order open type base and 61--4090 enclosure.

Bulletin Number

Description

Rods or

Wires Used

61BD1- 1000

Probe fitting with rubber cap

1

61LF1- 1000

Probe fitting in cast enclosure

61LF1- 1000M

61LJ2- 1000

Two probe fittings in cast enclosure

2

61LJ2- 1000M

Note: 61 Series probe fittings require suitable Series 64 probe tips and probe rod or suspension wires shown below.

63GH1- 1000

Special sanitary probe with 3 ft (0.91 m)
probe rod(s) supplied with 10 ft (3 m)
cable and separable connector

1

63GH2- 1000

2

63GJ1- 1000

1

63GJ2- 1000

2

Bulletin Number

Description

64CR1- 1000

Probe Tip and 1/4 in. dia. x 12 in. (0.3 m) Probe Rod

64CR1- 1001

Probe Tip and 1/4 in. dia. x 24 in. (0.61 m) Probe Rod

64CR1- 1002

Probe Tip and 1/4 in. dia. x 36 in. (0.91 m) Probe Rod

64CR1- 1003

Probe Tip and 1/4 in. dia. x 48 in. (1.22 m) Probe Rod

64CR1- 1004

Probe Tip and 1/4 in. dia. x 72 in. (1.83 m) Probe Rod

64CR1- 1005

Probe Tip and 1/4 in. dia. x 96 in. (2.44 m) Probe Rod

64CR1- 1006

Probe Tip and 1/4 in. dia. x 120 in. (3 m) Probe Rod

Installation

The control point for liquid level is the point at which the liquid makes
or breaks contact with the probe tip and is determined by the length of
the probe rod. Rods may be ordered to size, or may be supplied longer
than required and cut to the desired length. One end of the rod is
threaded for connection to the probe fitting. The unthreaded (cut) end
should be inserted in the probe tip and held by means of a set screw.

For deep well and other long probe applications over 10 ft (3 m),
suspension wires and tips should be installed. Standard probe tip
61­3288, is used with all probe rods. Special probe tip 61--3284 with
insulating sleeve, is used with suspension wire.

The probe rod or suspension wire adaptor 61--3285 is connected to the
probe fitting as follows:

61 Series fittings have a 1/4--20 female thread to receive the 1/4--20 male
thread of the probe rod or suspension wire adaptor.

When the long probe of any multiple probe assembly is over 30 in.
(0.76 m), a Teflon insulating spacer 31--224, is fitted over the short probe
rod immediately above the probe tip to prevent the rods from touching.
For suspension wire assemblies, an insulating sleeve fits over the probe
tip to prevent it from touching other surfaces.

Series 63 sanitary probes for dairy and food industry applications are
made for special sanitary fittings. The probe insulator is made to fit a #15
union ferrule and to be secured with a #13H union nut. The ferrule and
nut are supplied by the customer and are soldered, brazed, or otherwise
secured before insertion of the probe assembly. Probes 63GH1 and 63GH2
fit 1--1/2 in. ferrule, while probes 63GJ1 and 63GJ2 fit a 2 in. ferrule. All
Series 63 probe rods are 3 ft (0.91 m) long and are to be cut to length on
the job.

Mounting

The 13DJ3 controls may be mounted in any position on a sturdy wall,
partition, panel board, bracket, or similar support. While the NEMA
enclosure is being mounted, the control base should be stored in a safe
place to avoid moisture and mechanical damage.

The enclosure mounting hole dimensions are shown on page 12 and
sheet metal, wood or machine screws, bolts, or similar fasteners may be
used. When the housing has been securely fastened, connect the cables or
conduits to the housing in the knock out holes provided and replace the
control base.

The wiring between the control and the probes should not exceed the
lengths listed below.

Table 8: Maximum Recommended Cable Length

Range

Cable Length

1

2000 ft (609.6 m)

2

1000 ft (304.8 m)

3

500 ft (152.4 m)

4

2000 ft (609.6 m)

5

2000 ft (609.6 m)

6

150 ft (45.7 m)