Step 3: remove the scr module leg assemblies – Rockwell Automation 20P PowerFlex DC Drive - Frame D Snubber Resistors User Manual

Page 4

Advertising
background image

Publication 20P-IN066A-EN-P

4

Step 3: Remove the SCR
Module Leg Assemblies

Important: Note the terminal number on the fuse switch to which the signal

wires are connected for proper re-installation.

1. Remove the signal wires from the fuse switch connectors and secure the

wires in a position above the input terminals.

2. Loosen the lower bolt and washer that secures the bottom of each leg fuse to

the SCR module leg input terminal.

3. Loosen the upper bolt and washer that secures the top of the fuse to the AC

input terminal, rotate the top of the fuse out and downward, and remove the
fuse from the lower terminal.

1

4
2

Note terminal numbers on
fuses for wire connections

SCR module leg
input terminal

Main input terminal

Loosen upper bolts

Loosen lower bolts
and washers

Remove wires from
fuse switch terminals

Rotate top of fuse out and downward lift off lower terminal

Advertising