Rockwell Automation 193/592-EC1/EC3/EC5 E3 and E3 Plus Solid-State Overload Relay - Quick Reference User Manual

Page 21

Advertising
background image

21

Publication 193-QR003B-EN-P - October 2009

➊ The inhibit time setting parameters are applicable to both the trip and warning functions.

Overload warning setting is entered as a percentage of the thermal capacity utilized.

➌ Must use Ground Fault Sensors (Cat. No. 193-CBCT_).
➍ 50…100% for devices with FRN 1.003 and earlier.
➎ Available on 193/592-EC5 only.

Table 4: Warning Summary

Warning
Function

Warning

Enable

Factory
Default

Warning Level Settings

Inhibit Time Settings

Range Default

Range

Default

Overload

Disabled

0…100%➋

85%

Phase Loss

Ground Fault (193/592-EC2)

Disabled

Internal 1…5

A

2.0 A

0…250 s

10 s

Ground Fault (193/592-EC3)

Disabled

External

0.02…5 A ➌

2.0 A

0…250 s

10 s

Stall

Jam

Disabled

50…600%

150%

0…250 s

10 s

Underload

Disabled

10…100%➍

70%

0…250 s

10 s

Thermistor (PTC)

Disabled

Current Imbalance

Disabled

10…100%

20%

0…250 s

10 s

Comm Fault

Disabled

Comm Idle

Disabled

Voltage Input Module
Hardware Fault r

Enabled

Under Voltage L-L r

Disabled

0...65535

400

0…250 s

10 s

Over Voltage L-L ➎

Disabled

0...65535

490

0…250 s

10 s

Voltage Unbalance ➎

Disabled

0…100

85

0…250 s

10 s

Phase Rotation ➎

Disabled

1…2

1

0…250 s

10 s

Under Frequency ➎

Disabled

0…250

58

0…250 s

10 s

Over Frequency ➎

Disabled

0…250

62

0…250 s

10 s

Under Real Power ➎

Disabled

0…32767

0…250 s

10 s

Over Real Power ➎

Disabled

0…32767

0…250 s

10 s

Under Consumed kVAR ➎

Disabled

0…32767

0…250 s

10 s

Over Consumed kVAR ➎

Disabled

0…32767

0…250 s

10 s

Under Generated kVAR ➎

Disabled

-32767…0

0…250 s

10 s

Over Generated kVAR ➎

Disabled

-32767…0

0…250 s

10 s

Under Power kVA ➎

Disabled

0…32767

0…250 s

10 s

Over Power kVA ➎

Disabled

0…32767

0…250 s

10 s

Under Power Factor Lagging ➎

Disabled

-100…0

-95

0…250 s

10 s

Over Power Factor Lagging ➎

Disabled

-100…0

-90

0…250 s

10 s

Under Power Factor Leading ➎

Disabled

0...100

95

0…250 s

10 s

Over Power Factor Leading ➎

Disabled

0...100

90

0…250 s

10 s

Advertising