Table 8: Warning Summary

Warning
Function

Warning

Enable

Factory
Default

Warning Level

Settings

Warning Delay Settings

Inhibit Time

Settings

Range

Default

Range

Default

Range

Default

Ground Fault

Disabled

0.02…5 A

2.0 A

0.0…25 s

0.0 s

0…250 s

10 s

L1
Undercurrent

Disabled

0.2…45 A

0…250 s

1.0 s

L2
Undercurrent

Disabled

0.2…45 A

0…250 s

1.0 s

L3
Undercurrent

Disabled

0.2…45 A

0…250 s

1.0 s

L1
Overcurrent

Disabled

0.4…270 A

0…250 s

1.0 s

L2
Overcurrent

Disabled

0.4…270 A

0…250 s

1.0 s

L3
Overcurrent

Disabled

0.4…270 A

0…250 s

1.0 s

L1 Loss

Disabled

0…250 s

1.0 s

L2 Loss

Disabled

0…250 s

1.0 s

L3 Loss

Disabled

0…250 s

1.0 s

Comm Fault

Disabled

Comm Idle

Disabled

Remote Trip

Disabled