160 Series C Custom Firmware

Accel/Decel Selection

In addition to the two standard accel/decel times, a third set of
programmable accel/decel times has been added. None of these times
will be associated with the Preset Frequency parameters in the
standard drive. Instead, two other parameters will set the frequency
points where the different accel/decel times will be in affect (refer to
the

Table B

).

Table B
Accel/Decel Parameters

If P80 - [Mid to High Crossover] is less than P73 - [Low to Mid Crossover],
then P80 will be ignored and P67 - [Mid Accel] & P68 - [Mid Decel] will
be used for all frequencies above P73. If P73 is equal to zero, P30 -
[Low Accel] & P31 - [Low Decel] will not be used. See the following
diagram.

Parameter
Number

Parameter Name

Min./Max./Default

Description

P30

Low Accel

0.0/600.0/10.0 Sec

Accel used when frequency is
below first crossover point (P79).

P31

Low Decel

0.1/600.0/10.0 Sec

Decel used when frequency is
below first crossover point (P79).

P67

Mid Accel

0.0/600.0/20.0 Sec

Accel used when frequency is
between first & second crossover
points (P79 & P80).

P68

Mid Decel

0.1/600.0/20.0 Sec

Decel used when frequency is
between first & second crossover
points (P79 & P80).

P69

High Accel

0.0/600.0/30.0 Sec

Accel used when frequency is
above second crossover point
(P80).

P70

High Decel

0.1/600.0/30.0 Sec

Decel used when frequency is
above second crossover point
(P80).

P73

Low to Mid Crossover 0/240/30 Hz

First frequency crossover point
used to determine which accel/
decel rate will be used.

P80

Mid to High Crossover 0/240/60 Hz

Second frequency crossover
point used to determine which
accel/decel rate will be used.

P30
P31

P73

P67
P68

P69
P70

Frequency

P80