160 Series C Custom Firmware

Program Lock Password

The S02 option provides a program lock feature with a three digit
integer (standard lock feature uses a single digit). All program group
parameters will be locked unless the correct integer is entered in P57 -
[Program Lock]. This parameter value will re-initialize to “000” or re-
lock whenever power is cycled. The program unlock will also be
required when using communication modules after the power is
cycled.

Relay Output Contacts

Parameters P47 - [Output Configure] and P48 - [Output Threshold] are not
used with the S02 option. Instead, the relay will function to indicate a
balanced condition after the balance test has been completed and to
indicate the braking mode until shut-off. A switching of the relay
contacts from the de-energized state will indicate a balanced
condition at the balance frequency or the braking mode.

Summary of Parameter
Changes

The following parameter changes have been made to the standard 160
Analog Signal Follower Drive.

Parameter
Number

Standard Analog
Drive Parameter Name What Changed?

20

New parameter

Smartspin Angle, see

“Smartspin Balance Detection” on page 3

30

Accel Time 1

Changed to Low Accel, see

“Accel/Decel Selection” on page 2

31

Decel Time 1

Changed to Low Decel, see

“Accel/Decel Selection” on page 2

38

Boost Select

Changed to Smartspin Level, see

“Smartspin Balance Detection” on page 3

41

Motor Overload Select

Changed to Balance Volts, see

“Smartspin Balance Detection” on page 3

43

Current Limit

Changed to Low Speed Current Limit, see

“High Speed Stall Prevention” on page 1

46

Input Mode

Min./Max./Default changed to 0/8/0

47

Output Configure

Changed to High Speed Current Limit, see

“High Speed Stall Prevention” on page 1

48

Output Threshold

Changed to DC Injection Current Limit, see

“Braking” on page 4

49

PWM Frequency

Min./Max./Default changed to 2.0/6.0/4.0

57

Program Lock

Min./Max./Default changed to 000/999/000 - see

“Program Lock Password” on page 6

62

New parameter

Smartspin Status, see

“Smartspin Balance Detection” on page 3

63

New parameter

Smartspin Time, see

“Smartspin Balance Detection” on page 3

64

New parameter

Smartspin Freq, see

“Smartspin Balance Detection” on page 3

65

New parameter

Smartspin Result, see

“Smartspin Balance Detection” on page 3

66

New parameter

Smartspin Scale, see

“Smartspin Balance Detection” on page 3

67

New parameter

Mid Accel - see

“Accel/Decel Selection” on page 2

68

New parameter

Mid Decel - see

“Accel/Decel Selection” on page 2

69

Accel Time 2

Changed to High Accel, see

“Accel/Decel Selection” on page 2

70

Decel Time 2

Changed to High Decel, see

“Accel/Decel Selection” on page 2

73

Reverse Disable

Changed to Low to Mid Crossover, see

“Accel/Decel Selection” on page 2

80

Stall Fault Time

Changed to Mid to High Crossover, see

“Accel/Decel Selection” on page 2

81

PI Proportional Gain

Changed to Start Frequency, see

“Five Point V/Hz Curve” on page 4

82

PI Integral Gain

Changed to Start Volts, see

“Five Point V/Hz Curve” on page 4

83

PI Process Reference

Changed to Breakpoint1 Frequency, see

“Five Point V/Hz Curve” on page 4

84

PI Dead Band

Changed to Breakpoint1 Volts, see

“Five Point V/Hz Curve” on page 4

85

New Parameter

Breakpoint2 Frequency, see

“Five Point V/Hz Curve” on page 4

86

New Parameter

Breakpoint2 Volts, see

“Five Point V/Hz Curve” on page 4

Shading indicates recent firmware changes