S4 = stop time configuration – Rockwell Automation 150-SM6 SMC-50 Soft Starter Parameter Configuration Option Module Installation User Manual

Page 3

Advertising
background image

PN-164974
DIR 10000152879 (Version 01)
Publication 150-IN053B-EN-E

150-SM6 Switch Position Identification:

The following defines the functions of the 5 Rotary Switches:

S1 = Initial Torque Configuration:

S2 = Current Limit Configuration:

S3 = Ramp Time Configuration- Starting:

Rotary Switch S1 Position Setting

Resulting Initial Torque Value (in % Motor Torque)

0 10
1 16
2 22
3 28
4 34
5 40
6 46
7 52
8 58
9 64

A 70

(Default)

B 76
C 82
D 88
E 94

F 100

Rotary Switch S2 Position Setting

Resulting Current Limit Value (in % Motor

FLC

)

0 200
1 220
2 240
3 260
4 280
5 300
6 320
7 340
8 360

(Default)

9 380

A 400
B 420
C 440
D 460
E 480
F 500

Rotary Switch S3 Position Setting

Starting Ramp Time (in Seconds)

0 0.1
1 2
2 4
3 6
4 8
5 10

(Default)

6 12
7 14
8 16
9 18

A 20
B 22
C 24
D 26
E 28

30

S4 = Stop Time Configuration:

Rotary Switch S4 Position Setting

Stop Time (in Seconds 1 )

0

Coast to Stop (Default)

1 2
2 4
3 6
4 8
5 10
6 12
7 14
8 16
9 18

A 20
B 22
C 24
D 26
E 28

F 30

F

1) When the “Braking” STOP MODE is selected (Device Configuration Bank Switch #3 and #4) the controller multiplies the selected “Stop Time” by 10.
Refer to Device Configuration Switch Bank.