S5 = Motor FLC (Full Load Current) Configuration:

Rotary Switch S

5

Position Setting

% of Controller’s Max FLC

(1)

(2)

0 40

(Default)

1 44
2 48
3 52
4 56
5 60
6 64
7 68
8 72
9 76

A 80
B 84
C 88
D 92
E 96

F 100

(1) Since a set of switches do not provide the resolution to enter all possible Motor FLC combinations like a keypad, Switch S5 allows you to configure the
Motor’s FLC in the SMC50 by using a percent (%) of the controllers raed (e.g 90A, 110A, 140A, 180A, etc) FLC.

-

Example: For a 60A motor and a 90A controller, the % of Controller’s max FLC for 60A would be 64% of 90A (57.6A) or switch position 6.

(2) To determine the S5 switch setting for an inside the delta motor configuration use the following 2 equations:

Motor Nameplate

FLC

1

.

73

X

Step 1

:

Step 2

:

X

SMC - 50

Controller Rating

S5 Switch

Setting

100A

1.73

57.8A

Step 1:

Step 2

:

57

.

8 A

90A

Example:

64 %

S5 = Position 6

X 100

X 100

NOTE:

Switch Number

#1

#2

#3

#4

#5

#6

#7

#8

Start

Mode

Linear Speed Accel (Default)

0

0

Current Limit

0

1

Soft Start

1

0

Pump Start

1

1

Stop Mode

(1)(2)

Linear Speed Decel (Default)

0

0

Soft Stop

0

1

Braking

1

0

Pump Stop

1

1

Energy Saver

Enable

1

Disable (Default)

0

Braking

Current

50%

0 0 0

100%

0 0 1

150%

0 1 0

200%(Default)

0 1 1

250%

1 0 0

300%

1 0 1

350%

1 1 0

400%

1 1 1

1) If the calculated value doesn’t match a switch position use the previous (lower percent) switch setting
2) The inside the delta motor configuration can be selected using Parameter 44 (Motor Connection) or automatically during a controller Tuning process.

The following defines the functions of the 3 banks of On/Off 8-switch DIP switches. Each of the 3 banks is defined by

a high level functional name (e.g. Device, I/O and Protection) with each switch having a unique function.

Device Configuration Bank (0=OPEN):