• Motor Does Not Start

(No output voltage to motor)

1. Check power circuit.

- Check supply voltage.
- Check all fuses and disconnects.

2. Check the motor –

Verify that it is connected properly.

3. Check control input signals.

- Verify that START signal is present.
- Verify that the contact closure signal is present at TB3-8.
- Verify that either the RUN FORWARD or RUN REVERSE signal

is active, but NOT both.

4. Check P46 - [Input Mode].

- If P46 - [Input Mode] is set to 2, only the program keypad

module Start button will start the motor.

5. Cycle power or use P56 - [Reset Functions] if you changed

P46 - [Input Mode].

• Drive Started but Motor NOT Rotating

(P01 - [Output Frequency] displays “0.0”)

1. Check the motor –

Verify that it is connected properly.

2. Check frequency source P06 - [Frequency Command].

- Verify that a frequency signal is present at terminal block

TB3. Either a –10 to +10V or 4-20 mA signal.

- Verify that Preset Frequencies are set properly.

3. Check control input signals.

- Verify that SW1, SW2 and SW3 are correct. (Refer to the

chart in the User Manual at the end of Chapter 5).

4. Check parameter settings.

- Verify that P59 - [Frequency Select] is showing the desired

frequency source.

- Verify that P58 - [Internal Frequency] is the desired value.

5. Cycle power or use P56 - [Reset Functions] if you changed

P46 - [Input Mode].

• Motor Not Accelerating Properly

1. Check the motor –

Verify that it is connected properly and that

no mechanical problems exist.

2. Check parameter settings.

- Verify that P30 - [Accel Time 1] or P69 - [Accel Time 2]

(whichever is current used) is set properly.

- Verify that P43 - [Current Limit] is set properly.
- Verify that P38 - [Boost Select] is set properly.

• Can Not Operate in “RUN FWD/RUN REV” Mode

1. Verify that P46 - [Input Mode] is set to 1.

2.

Verify that the contact closure signal is present at TB3-8

.

3. Verify that P73 - [Reverse Disable] and P74 - [Analog

Select] are not set to 1.

4. Verify that power has been cycled for above change to take

effect.

5. Verify that both RUN FORWARD and RUN REVERSE switches

are NOT closed simultaneously.

6. Cycle power or use P56 - [Reset Functions] if you changed

P46 - [Input Mode].

Control Wiring – TB3

Power Wiring – TB1, TB2

Control Wiring

TB3

Motor & Capacitor
Module Wiring

TB2

Line Power & Dynamic
Brake Module Wiring

TB1

SEL

ESC

DC+

W/T3

1

3 4 5 6 7 8 9 10 11

2

V/T2

U/T1

DC–

BR+

T/L3

S/L2

R/L1

BR–

Required Branch

Circuit Disconnect

Dynamic Brake

Module (optional)

Capacitor Module

(optional)

Input Line

Protective Device

TB2

TB1

PE

BR+

T/L3

S/L2

R/L1

BR–

DC+

W/T3

V/T2

U/T1

DC–

Motor

Wire Size and Torque Ranges

For single phase input applications, connect the AC input line to input terminals
S (L2) and T (L3).

10V DC Supply

Wiper

Common

4 – 20 mA Input

Reverse

Start

Common

Stop/Programmable

Normally Closed

Relay Common

Normally Open

SW1

SW2

Common

SW3

Run Reverse

Run Forward

Common

Stop/Programmable

Normally Closed

Relay Common

Normally Open

Three-Wire Control Shown

(Factory Default)

Two-Wire Control Shown

(Factory Default is Three-Wire)

1

23

4

56

7

89

10

11

1

23

4

56

7

89

10

11

N.O. Momentary Contact

N.C. Momentary Contact

N.O. Maintained Contact

N.C. Maintained Contact

Wires must be shielded.

Preset Speed Model

Analog Signal Follower Model

Model

4.0 kW (5 HP)
Three Phase

1.5 kW (2 HP)
Single Phase

All Other Ratings

Terminal

TB1, TB2
TB3
TB1, TB2
TB3

TB1, TB2
TB3

Min./Max. Wire Size

mm

2

(AWG)

5.26-3.31 (10-12)
2.50-0.50 (14-22)
5.26-3.31 (10-12)
2.50-0.50 (14-22)
3.31-0.82 (12-18)
2.50-0.50 (14-22)

Min./Max. Torque

Nm (lb.-in.)

1.35-0.90 (12-8)
0.80-0.40 (8-4)
1.35-0.90 (12-8)
0.80-0.40 (8-4)
1.35-0.90 (12-8)
0.80-0.40 (8-4)

Troubleshooting