Program Group Parameters

No.

Parameter Name

Min/Max Range Units/Settings

Default

30

[Accel Time 1]

0.0-600

0.1 Sec

10.0

31

[Decel Time 1]

0.1-600

0.1 Sec

10.0

32

[Min. Freq.]

0-240

1 Hz

0

33

[Max. Freq.]

0-240

1 Hz

60

34

[Stop Mode Select]

0-3

0 = Ramp

0

1 = Coast
2 = DC Brake
3 = DC Brake Auto-Off

35

[Base Freq.]

10-240

1 Hz

60

36

[Base Voltage]

20-230/460

1 Volt

230/460

37

[Max. Voltage]

20-255/510

1 Volt

230/460

38

[Boost Select]

0-12

Start Volts (%) Midpoint (%) 2
0 = 0

9 = 45.0

1 = 2.5

10 = 40.0

2 = 5.0

11 = 35.0

3 = 7.5

12 = 30.0

4 = 10.0
5 = 12.5
6 = 15.0
7 = 17.5
8 = 20.0

39

[Skip Freq.]

0-240

1 Hz

240

40

[Skip Freq. Band]

0-30

1 Hz

0

41

[Motor Overload Select] 0-2

0 = No Derating

0

1 = Min. Derating
2 = Max. Derating

42

[Motor Overload Current] 0.1-200% of

0.01 Amps

115% of

Drive Rating

Rating

43

[Current Limit]

1-180% of

1%

150%

Drive rating

44

[DC Hold Time]

0-25

0.1 Sec

0

45

[DC Hold Voltage]

0-115

1 Volt

0

46

[Input Mode]

0-9

0 = 3-wire control

0

1 = 2-wire control
2 = Keypad control
3 = Momentary FWD/REV control
4 = 2-wire “Accel/Decel” control
5 = 2-wire Coast to Rest control
6 = 2-wire TB3/Keypad-Comm control
7 = 2-wire P59-[Frequency Select] control
8 = 2-wire Preset Speed control
9 = 2-wire PI control

47

[Output Configure]

0-10

0 = Drive Ready/Faulted

0

1 = At Frequency
2 = Motor Running
3 = Reverse
4 = Motor Overload
5 = Ramp Regulated
6 = Above Frequency
7 = Above Current
8 = Above DC Bus Voltage
9 = Retries Exhausted
10 = Above Power Factor Angle

48

[Output Threshold]

0-815

P47 - 6 = 0-240 Hz Range

0

P47 - 7 = 0-180% Range
P47 - 8 = 0-815 V Range
P47 - 10 = 0-180°

49

[PWM Freq.]

2.0-8.0

0.1 kHz

4.0

50

[Restart Tries]

0-9

Numeric Value

0

51

[Restart Time]

0.5-300

0.1 Sec

10.0

52

[DB Enable]

0-100

0 = Disable, > 0 = % of dB

0

53

[S-Curve]

0-10

0, 1...10 @ 10% Increments 0

54

[Clear Fault]

0-1

1 = Reset fault

0

55

[Memory Probe Address] Numeric Value

Numeric Value

Numeric

56

[Reset Functions]

0-2

0 = Idle State

0

1 = Reset Defaults
2 = Update Input Mode

Display Group Parameter List

Program Group Parameters

(continued)

No.

Parameter Name

Min/Max Range Units/Settings

Default

57

[Program Lock]

0-1

0 = Unlock

0

1 = Lock

58

[Internal Freq.]

0-240

0.1 Hz

60

59

[Freq. Select]

0-1

0 = TB3

0

1 = Internal Freq.

60

[Zero Offset]

–50.0 to +50.0

0.1%

0

61-68 [Preset Freq.0 – 7]

0-240

0.1 Hz

See Below

69

[Accel Time 2]

0.0-600

0.1 Sec.

20.0

70

[Decel Time 2]

0.1-600

0.1 Sec.

20.0

71

[IR Compensation]

0-150

1%

50%

72

[Slip Compensation]

0.0-5.0

0.1 Hz

2.0 Hz

73

[Reverse Disable]

0-1

0 = Enable

0

1 = Disable

74

[Analog Select]

0-1

0 = Unipolar

0

1 = Bipolar

75

[Analog Input Min.]

0.0-150.0

0.1%

0.0%

76

[Analog Input Max.]

0.0-150.0

0.1%

100%

78

[Compensation]

0-2

Numeric Value

0

79

[Software Current Trip]

0-50%

1%

0

80

[Stall Fault Time]

0-5

0 = Normal (Appx. 60 sec)

0

1 = 2 x Normal
2 = 4 x Normal
3 = 6 x Normal
4 = 8 x Normal
5 = Disable

81

[PI Proportional Gain]

0-10.00

Numeric Value

0.01

82

[PI Integral Gain]

0-10.00

Numeric Value

0.01

83

[PI Process Reference]

0-100.0%

0.1%

0.0%

84

[PI Dead Band]

0-10.0%

0.1%

0.0%

Status of Bit 3 for P46 - [Input Mode] setting 8 (TB3-2) is 0 = Open, 1 = Closed.

Parameters 63, 64, 67 & 68 apply to the Preset Speed model only.

This parameter setting applies to the Analog Signal Follower model only.

When using P46 - [Input Mode] setting 4, the Accel and Decel times are selected
by providing an input to TB3-8.

In firmware 7.05, there are minimum decel settings based on horsepower. 1 HP
and less remain 0.1 seconds, 2 HP is 0.2 seconds, 3 HP is 0.6 seconds, and 5 HP
is 0.7 seconds.

In firmware 7.06, all Input Modes of parameter 46 allow PI control except Input
Mode 8.

Program Group Parameter List

Display Group Parameters

No.

Parameter Name

Min/Max Range

Units/Settings

01

[Output Frequency]

0-240 Hz

0.1 Hz

02

[Output Voltage]

0-Max Voltage

1 Volt

03

[Output Current]

0-2 x Rtd. Out. Curr. 0.01Amps

04

[Output Power]

0-2 x Rtd. Out. Power 0.01 kW

05

[Bus Voltage]

0-400 (230V)

1 Volt

0-800 (460V)

06

[Frequency Command] 0-240

0.1 Hz

07

[Active Fault]

0-48

Numeric Value

08

[Heatsink Temperature] 69-150

1 Degree C

09

[Controller Status]

0000 to 1011

Bit 3

Bit 2

Bit 1

Bit 0

Decel Accel Forward

Running

10

[Controller Type]

Numeric Value

Numeric Value

11

[Control Version]

Fixed Value

Numeric Value

12

[Input Status]

0000 to 1111

See Below

13

[Power Factor Angle]

0.0-180.0

0.1 Degrees

14

[Memory Probe Display] Numeric Value

Numeric Value

15

[Preset Status]

0000 to 0111

Bit 3

Bit 2

Bit 1

Bit 0

Not Used SW3

SW2

SW1

16

[Analog Input]

–150 to +150

0.1%

17

[Fault Buffer 0]

0-48

Numeric Value

18

[Fault Buffer 1]

0-48

Numeric Value

19

[Fault Buffer 2]

0-48

Numeric Value

1

TB3

2

3

4

5

6

7

8

9

10

11

Description
3-Wire
2-Wire
Keypad
Mom. Run Fwd/Rev
Accel/Decel

Coast to Rest
TB3/Keypad or Comm.

Frequency Select

SF1 Preset Speed

2-Wire PI Control

Bit 3
0 = Positive
Analog Input

1 = Negative
Analog Input

TB3-8
Bit 1
Stop
Stop
Stop
Stop
0=Accel 2/Decel 2
1=Accel1/Decel 1
Coast to Rest Stop
0=TB3 Control
1=Keypad or Comm.
0=Analog Freq. Select
1=Internal Freq. Select
0=Open
1=Closed
0=PI
1=Internal Freq. Select

P46
Input
Mode
0
1
2
3
4

5
6

7

8

9

TB3-6
Bit 2
Start
Run Forward
N/A
Run Forward
Run Forward

Run Forward
Run Forward

Run Forward

Run Forward

Run Forward

TB3-5
Bit 0
Reverse
Run Reverse
N/A
Run Reverse
Run Reverse

Run Reverse
Run Reverse

Run Reverse

Run Reverse

Run Reverse

Bit 1

Bit 2

Bit 0

3

2

1

TB3

4

5

6

7

8

9

10

11

Name
[Preset 0]
[Preset 1]
[Preset 2]
[Preset 3]
[Preset 4]
[Preset 5]
[Preset 6]
[Preset 7]

Default
3 Hz
20 Hz
30 Hz
40 Hz
45 Hz
50 Hz
55 Hz
60 Hz

Accel

Parameter 30,
[Accel Time 1]

Parameter 69,
[Accel Time 2]

Decel

Parameter 31,
[Decel Time 1]

Parameter 70,
[Decel Time 2]

No.
61
62
63
64
65
66
67
68

TB3-2
(SW2)

0
0
1
1
0
0
1
1

TB3-1
(SW1)

0
1
0
1
0
1
0
1

TB3-4
(SW3)

0
0
0
0
1
1
1
1

Preset Speed

Model

Signal Follower

Model

TB3-8
(SW2)

0
0

N/A
N/A

1
1

N/A
N/A

TB3-2
(SW1)

0
1

N/A
N/A

0
1

N/A
N/A

SW3

SW2

SW1

(Preset Speed Model Designations Shown)